Install Manual

TP-6906 6/1418 Section 1 Installation Instructions
1.4.2 Terminal Connector Torque
Use the torque values shown in Figure 1-7 or Figure 1-8
for terminal connectors. Refer to UL-486A, UL-486B,
and UL-486E for information on terminal connectors for
aluminum and/or copper conductors. Comply with
applicable national, state, and local codes when
installing a wiring system.
Note: If a connector has a clamp screw such as a
slotted, hexagonal head screw with more than
one means of tightening, test the connector using
both applicable torque values provided in
Figure 1-8.
Socket Size Across
Flats, mm (in.)
Tightening Torque,
Nm (in. lb.)
3.2 (1/8) 5.1 (45)
4.0 (5/32) 11.4 (100)
4.8 (3/16) 13.8 (120)
5.6 (7/32) 17.0 (150)
6.4 (1/4) 22.6 (200)
7.9 (5/16) 31.1 (275)
9.5 (3/8) 42.4 (375)
12.7 (1/2) 56.5 (500)
14.3 (9/16) 67.8 (600)
Note: For values of slot width or length not corresponding to
those specified, select the largest torque value
associated with the conductor size. Slot width is the
nominal design value. Slot length is to be measured at
the bottom of the slot.
Figure 1-7 Tightening Torque for Pressure Wire
Connectors with Internal-Drive
Socket-Head Screws
Wire Size for Unit
Connection
Tightening Torque, Nm (in. lb.)
Slot Head 4.7 mm (No. 10) or Larger*
Hexagonal Head—External
Drive Socket Wrench
AWG, kcmil (mm
2
)
Slot Width <1.2 mm (0.047 in.)
Slot Length <6.4 mm (0.25 in.)
Slot Width >1.2 mm (0.047 in.)
Slot Length >6.4 mm (0.25 in.)
Split-Bolt
Connectors
Other
Connections
18--10 (0.82--5.3) 2.3 (20) 4.0 (35) 9.0 (80) 8.5 (75)
8 (8.4) 2.8 (25) 4.5 (40) 9.0 (80) 8.5 (75)
6--4 (13.3--21.2) 4.0 (35) 5.1 (45) 18.6 (165) 12.4 (110)
3 (26.7) 4.0 (35) 5.6 (50) 31.1 (275) 16.9 (150)
2 (33.6) 4.5 (40) 5.6 (50) 31.1 (275) 16.9 (150)
1 (42.4) 5.6 (50) 31.1 (275) 16.9 (150)
1/0--2/0 (53.5--67.4) 5.6 (50) 43.5 (385) 20.3 (180)
3/0--4/0 (85.0--107.2) 5.6 (50) 56.5 (500) 28.2 (250)
250--350 (127--177) 5.6 (50) 73.4 (650) 36.7 (325)
400 (203) 5.6 (50) 93.2 (825) 36.7 (325)
500 (253) 5.6 (50) 93.2 (825) 42.4 (375)
600--750 (304--380) 5.6 (50) 113.0 (1000) 42.4 (375)
800--1000 (406--508) 5.6 (50) 124.3 (1100) 56.5 (500)
1250--2000 (635--1016) 124.3 (1100) 67.8 (600)
* For values of slot width or length not corresponding to those specified, select the largest torque value associated with the conductor size.
Slot width is the nominal design value. Slot length is to be measured at the bottom of the slot.
Note: If a connector has a clamp screw such as a slotted, hexagonal head screw with more than one means of tightening, test the
connector using both applicable torque values.
Figure 1-8 Tightening Torque for Screw-Type Pressure Wire Connectors