TP-6906 6/1450 Section 3 Generator Reconnection
Volts L1--L2:
240 V
Volts L2--L3:
240 V
Volts L3--L1:
240 V
Generator ---->
Metering
Reset
Calibration
<---- Return
Reset
Calibration? No
Volts:
240V
Three-phase Single-phase
tp6811
Reset
Calibration? Yes
Frequency:
60.0 Hz
Frequency:
60.0 Hz
1. Press Select when the voltage is
displayed. The voltage flashes.
2. Press the Up or Down arrow but-
ton to change the s etting.
3. Press the Select button to save the
setting.
4. Press the down arrow button to
move to the next menu.
Calibrate
Calibrate
Calibrate
Calibrate
Note: Pressing select when Reset Calibration: Yes is displayed will discard
the changes and reset the calibration to the original settings.
To Calibrate Voltage:
Figure 3-6 Voltage Calibration