Full Product Manual

TP-7092 4/23 73
Figure 56 Oil Fill Components
4. Check for leaks.
a. Check for oil leaks.
b. Fix leaks and recheck the oil level.
c. Reinstall the housing side panel.
5. Reset the maintenance timer on the controller.
4.2.6 Resetting the Maintenance Timer
1. From the Overview menu, step down to the Genset Run Time menu.
2. Press the Select button and then step down to the Next Maintenance screen.
3. Press the Select button.
4. Press the Up arrow button so that “Reset Maint Timer? Yes” is displayed.
5. Press the Select button. After about two minutes, the new maintenance interval and date are displayed.
img1062
Dipstick
Note:
20 kW model shown; 14 kW and 26 kW models are similar.
Oil fill
Oil cooler located under shroud
(20 and 26 kW models)