Use and Care Manual

TP-6810 6/15 57Section 4 Scheduled Maintenance
4.6.4 Flushing an d Cleaning
For optimum protection, drain, flush, and refill the
cooling system at the interval listed in the service
schedule.
Flushing and Cleaning Procedure
1. Flush the system with clean water.
2. Drain, clean, and flush the coolant overflow bottle.
3. Refill the cooling system as instructed in
Section 4.6.5.
4.6.5 Filling Cooling System
Model
Coolant Capacity, L (qt.)
Generator Set With Block Heater
38RCL 15.5 (16.4) 17.0 (18.0)
38RCLA 17.5 (18.5) 19.0 (20.1)
48RCL 17.5 (18.5) 19.0 (20.1)
60RCL 17.5 (18.5) 19.0 (20.1)
Figure 4-6 Coolant Capacity
Note: Do not add coolant to a hot engine. Adding
coolant to a hot engine can cause the cylinder
block or cylinder head to crack. Wait until engine
has cooled.
1. Close the radiator’s coolant drain valve and tighten
the hose clamps.
2. Fill the radiator with the recommended coolant
mixture of 50% ethylene glycol and 50% clean,
softened water to inhibit rust/corrosion and prevent
freezing. The coolant capacity is shown in
Figure 4-6.
3. Operate the engine with the radiator cap removed
until the thermostat opens and the upper radiator
hose becomes hot.
4. Stop the engine and allow it to cool.
5. Add coolant to the radiator to just below the
overflow tube on the filler neck. See Section 1,
Service Views, for the overflow tube location.
6. Replace the radiator’s pressure cap.
7. Maintain the coolant level in the coolant overflow
bottle between the High and Low markings. See
Section 1, Service Views, for the coolant overflow
bottle location.
8. Re--energize the block heater, if equipped.
4.7 Ignition System
Airborne particles.
Can cause severe injury or
blindness.
Wear protective goggles and clothing
when using power tools, hand tools,
or compressed air.
WARNING
Accidental starting.
Can cause severe injury or death.
Disconnect the battery cables before
working on the generator set.
Remove the negative (--) lead first
when disconnecting the battery.
Reconnect the negative (--) lead last
when reconnecting the battery.
WARNING
Disabling the generator set. Accidental starting can
cause severe injury or death. Before working on the
generator set or equipment connected to the set, disable the
generator set as follows: (1) Press the generator set off/reset
button to shut down the generator set. (2) Disconnect the
power to the battery charger, if equipped. (3) Remove the
battery cables, negative (--) lead first. Reconnect the negative
(--) lead last when reconnecting the battery. Follow these
precautions to prevent the starting of the generator set by the
remote start/stop switch.
Service the spark plugs at the interval specified in the
service schedule using the following procedure.
1. Press the OFF button on the RDC2 controller.
2. Disconnect the power to the battery charger.
3. Disconnect the generator set engine starting
battery, negative (--) lead first.
4. Remove spark plug wires by grasping the spark
plug boot and turning slightly while pulling. Do not
pull the wire. Pulling on the wire rather than the
boot may damage the wire or terminal.
5. Loosen the spark plug with a ratchet and 5/8-in.
spark plug socket with a rubber insert to prevent
spark plug damage.