Engine Manual

Table Of Contents
TP-7095 4/18 19
2.2.2 Fuel Specifications
Note:
The fuel system installation must comply with applicable national, state, and local codes.
Fuel Type
Item
Specification
KG6208
Liquid Propane Gas
(LPG)
Type
HD-5 or HD-10
Maximum fuel pressure (engine OFF, no load)
11.0” W.C.
Minimum fuel pressure (engine ON, full load)
5.0” W.C
Natural Gas (NG)
Supply
Standard pipeline
Approximate supply volume
37.257 kJ/m
3
(1000 BTU/ft.
3
)
Minimum flow
42.6 m
3
/hr. (1504 ft
3
/hr) @ 6.0” W.C.
Allowable water vapor
Less than 112.3 kg per 1 million m
3
(Less than 7 lb. per 1 million ft.
3
)
Maximum fuel pressure (engine OFF, no load)
11.0” W.C.
Minimum fuel pressure (engine ON, full load)
7.0” W.C.
LPG and NG (both)
Fuel handling and supply component constraints
UL 2200: Standard for Stationary Engine
Equipment Assemblies
Operating temperature range
0°C (32°F) to 45°C (113°F) Unaided
Figure 8 Fuel Specifications