Operation Residential/Light Commercial Generator Sets Model: 48RCLB 60RCLA Controller: RDC2 TP-7102 4/18a
California Proposition 65 California Proposition 65 WARNING Engine exhaust from this product contains chemicals known to the State of California to cause cancer, birth defects, or other reproductive harm. WARNING This product contains and/or emits chemicals known to the State of California to cause cancer, birth defects, or other reproductive harm. Kohler strongly recommends that only factory-authorized distributors or dealers install and service the generator.
Table of Contents Product Identification Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Safety Precautions and Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Table of Contents, continued 3.12 3.13 3.14 3.15 3.16 3.17 4 Genset Run Time Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Genset System Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ATS Status Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ATS Configuration Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Safety Precautions and Instructions IMPORTANT SAFETY INSTRUCTIONS. Electromechanical equipment, including generator sets, transfer switches, switchgear, and accessories, can cause bodily harm and pose life-threatening danger when improperly installed, operated, or maintained. To prevent accidents be aware of potential dangers and act safely. Read and follow all safety precautions and instructions. SAVE THESE INSTRUCTIONS.
metal surface away from the battery. To avoid sparks, do not disturb the battery charger connections while the battery is charging. Always turn the battery charger off before disconnecting the battery connections. Ventilate the compartments containing batteries to prevent accumulation of explosive gases. Battery short circuits. Explosion can cause severe injury or death. Short circuits can cause bodily injury and/or equipment damage. Disconnect the battery before generator set installation or maintenance.
Propane (LPG)—Adequate ventilation is mandatory. Because propane is heavier than air, install propane gas detectors low in a room. Inspect the detectors per the manufacturer’s instructions. Natural Gas—Adequate ventilation is mandatory. Because natural gas rises, install natural gas detectors high in a room. Inspect the detectors per the manufacturer’s instructions. Gas fuel leaks. Explosive fuel vapors can cause severe injury or death. Fuel leakage can cause an explosion.
Short circuits. Hazardous voltage/current will cause severe injury or death. Short circuits can cause bodily injury and/or equipment damage. Do not contact electrical connections with tools or jewelry while making adjustments or repairs. Remove all jewelry before servicing the equipment. Engine block heater. Hazardous voltage will cause severe injury or death. The engine block heater can cause electrical shock.
Introduction This manual provides operation instructions for Model 48RCLB and 60RCLA residential/light commercial generator sets equipped with the RDC2 generator set/transfer switch controller. This generator set is approved for use in stationary applications in locations served by a reliable utility power source. Have the generator set installed by an authorized Kohler distributor/dealer or service technician. Refer to the Installation Manual for installation instructions.
List of Related Literature Figure 3 identifies related literature available for the generator sets covered in this manual. Only trained and qualified personnel should install or service the generator set.
Service Assistance For professional advice on generator set power requirements and conscientious service, please contact your nearest authorized Kohler distributor or dealer. D Visit the Kohler Co. website at KOHLERPower.com. D Look at the labels and decals on your Kohler product or review the appropriate literature or documents included with the product. D Call toll free in the US and Canada 1-800-544-2444. D Outside the US and Canada, call the nearest regional office.
Notes 12 Service Assistance TP-7102 4/18
Section 1 Service Views 1 2 3 4 5 19 18 6 17 16 14 15 13 21 9 8 12 11 10 SERVICE SIDE 7 22 29 20 30 31 28 28 32 ADV-8954 27 7 26 25 24 23 Cooling System Detail NON-SERVICE SIDE 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16.
Notes 14 Section 1 Service Views TP-7102 4/18
Section 2 Generator Set Operation 2.1 Operating Area WARNING WARNING Carbon monoxide. Can cause severe fainting, or death. nausea, The exhaust system must be leakproof and routinely inspected. Carbon monoxide symptoms. Carbon monoxide can cause severe nausea, fainting, or death. Carbon monoxide is a poisonous gas present in exhaust gases. Carbon monoxide is an odorless, colorless, tasteless, nonirritating gas that can cause death if inhaled for even a short time.
WARNING Sulfuric acid in batteries. Can cause severe injury or death. Wear protective goggles and clothing. Battery acid may cause blindness and burn skin. WARNING Explosion. Can cause severe injury or death. Relays in the battery charger cause arcs or sparks. Locate the battery in a well-ventilated area. Isolate the battery charger from explosive fumes. Battery gases. Explosion can cause severe injury or death. Battery gases can cause an explosion.
Note: Block heater damage. The block heater will fail if the energized heater element is not immersed in coolant. Fill the cooling system before turning on the block heater. Run the engine until it is warm, and refill the radiator to purge the air from the system before energizing the block heater. Drive Belt(s). Check the belt condition of the water pump and battery charging alternator belt(s). Exhaust System. Check for exhaust leaks and blockages.
transfer switch. Also see Section 2.7, Model RXT Transfer Switch Operation. The RDC2 controller must be in AUTO mode for automatic transfer switch operation. Automatic Start The RDC2 controller receives utility source voltage sensing data from the Model RXT transfer switch. 1. If the utility source voltage falls below an acceptable level, the controller starts the engine start time delay. 2. If the utility source is not restored before the time delay expires, the generator set starts. 3.
Engine Speed, RPM 2.5.2 3 min. 1 min. Engine Exercise The unloaded full speed exercise runs the generator set at full speed for 20 minutes without transferring the load. To set an unloaded full speed exercise, follow the procedure in Figure 2-3 and select Exercise Mode: Unloaded Full. 1 min. 10 min. Unloaded Full-Speed Exercise 5 min. Full-Speed Diagnostics Cooldown Figure 2-1 Unloaded Exercise Cycle System Diagnostics During the unloaded cycle exercise, the controller monitors the following data.
If the utility power is lost during a loaded exercise, the exercise is ended. The ATS remains in the emergency position and the control goes into the AUTO mode. The generator set continues to run and supply power to the load for the duration of the utility power outage. When Utility power is restored, the ATS will re-transfer to the utility source through normal timing sequences. 2.5.
12. Set the exercise frequency (weekly or every two weeks). Weekly exercises are recommended. 13. Press the down arrow button to step to the Return menu. Press the Select button to return to the main menu. 14. Check that the AUTO LED is lit. The generator set must be in automatic mode for the exercise to run as scheduled. Status Displays After a scheduled exercise run, the next exercise time and date will be updated automatically based on the Exercise Frequency setting.
Genset System ----> System Voltage: 240 V System Freq: 60 Hz VR Voltage Adj: 240.0V System Phase: Single System Battery: 12 V Next Exercise * Next Exercise HR:MN PM MM/DD/YY HR:MN PM MM/DD/YY See Section 2.5.8, Changing the Exercise Setting Exercise Mode: Exercise Mode: Unloaded Cycle None/Unloaded Full Sp/ Unloaded Cycle/Loaded Full SP Exercise Freq: Exercise Freq: Weekly Weekly/Every Other Week Meas.
2.6 Faults Selected fault conditions are shown in Figure 2-5. Fault conditions are classified as warnings or shutdowns. If a fault occurs that is not listed in the table, contact an authorized distributor/dealer for service. the transfer switch has been lost. Check the connection to the ATS interface board. 2.6.
Fault AC Sens Lost Warning (W) or Shutdown (SD) Condition W (1 sec.) SD (3 sec.) AC Sensing Lost. In Auto mode, generator output AC sensing is lost. Starts 10 seconds after crank disconnect. Check Contact an authorized distributor/dealer for service. Warning: after 1 second if no output detected after crank disconnect. Shutdown: after 3 seconds if voltage was present and then lost. Accy PwrOver Warning W Accessory Power Overload.
Fault Warning (W) or Shutdown (SD) Condition Check Exer Not Sch W Exercise Not Scheduled. No exercise has been scheduled on the RDC2 controller. See Section 2.5 for instructions to set the exerciser. Generator Frequency High SD Governed frequency exceeds 110% of the system’s frequency setpoint for more than 10 seconds. Function becomes active 10 seconds after engine start (10 second inhibit). Contact an authorized distributor/dealer for service.
2.6.5 Event Log The event log displays up to 1000 controller faults and notices, starting with the most recent event. Events are numbered 1--1000, with 1 being the most recent. Each event is displayed with the date and time of the event, the number of the event, a code to indicate whether the event was a warning ( W), shutdown (S), or informational notice ( I), the engine hours at the time of the event, and the event description.
2.7.2 ATS Control Sequence of Operation 2.7.3 Time Delays Time delays are factory-set to the values shown in Figure 2-8. An authorized distributor/dealer can adjust time delays using a personal computer and Kohlerr SiteTecht software. See Figure 2-8 for time delay settings. Preferred Source Fails: Time delays described in this section operate only when the controller is connected to a Kohlerr Model RXT transfer switch. 1. The load control contact opens. 2. The engine start time delay times out. 3.
Notes 28 Section 2 Generator Set Operation TP-7102 4/18
Section 3 RDC2 Controller Operation 3.1 RDC2 Generator Set/Transfer Switch Controller Model 48RCLB and 60RCLA generator sets are equipped with the RDC2 generator set/transfer switch controller. The RDC2 controls the following power system components: 3.2 Controls and Indicators Figure 3-1 illustrates the keypad, display, and indicators on the controller’s user interface.
3.2.1 Controller Keypad The Run, Off, and Auto buttons control the generator set as described in Figure 3-2. Use the Select, Up arrow, and Down arrow buttons to navigate through the menus and change settings, if necessary. See Section 2.4 for operation instructions. 3.2.2 LED Indicators LEDs above the RUN, OFF, and AUTO buttons indicate the mode of operation as shown in Figure 3-2. The RDC2 controller also has a set of power system LEDs below the pushbuttons.
3.2.3 LCD Display The controller is equipped with a two-line x 16 character backlit liquid crystal diode (LCD) display with adjustable contrast. When the generator is running, the controller automatically scrolls through the displays shown in Figure 3-4. When the system is in AUTO, the LCD display scrolls through the status messages shown in Figure 3-5. When a fault or warning condition exists, the controller will show the corresponding message. See Section 2.
3.3 Controller Power The RDC2 controller is powered by the generator set engine starting battery and the built-in battery charger. Note: To disconnect controller power, disconnect the battery and the utility power to the generator set. If controller power is disconnected and reconnected, you will be prompted to set the time, date, and exerciser. The first setting will flash. Press the Up and Down arrow buttons to change the setting. Press Select to save the setting and move on to the next.
Changing Settings on the RDC2 Controller 1. Press the Select button to enter the main menu. Press: Display: Overview ----> 1.2 h Press: 2. Press the down arrow button until the desired menu is displayed. See Figure 3-7. Date and Time are used for this example. Press: Display: Date ----> Display: Display: Date: 05Jan2017 Date: 12Jan2018 9. Press the down arrow button to step to the next menu. Press: Display: and Time 3. Press the Select button to enter the Date and Time menu. Press: 8.
3.6 Controller Menus 3.7 Main Menu The following sections show the RDC2 controller menus and submenus. Use the Select button and the up and down arrow buttons to navigate the menus as shown in the diagrams. Press the Select button once to bring up the main menu. Overview is displayed. See Figure 3-7. Press the down arrow button to step to the next menu, Engine Metering. Use the UP and DOWN arrow buttons to step up and down through the menus shown in Figure 3-7.
3.8 Overview Menu Overview ----> 1.2 h 3.9 Engine Metering Menu The engine metering menu displays engine status information as shown in Figure 3-9. This menu displays status information only. No settings can be changed from this menu. Active Alert (if any) Engine ----> Metering Genset Status Standby Eng Speed: 1800 RPM Oil Pressure: 40 PSI Voltage: 240V Freq: 60.0Hz Coolant Temp: 73 F Engine: 95F Oil: 40 PSI Oil Temp: Battery 73 F 13.4V Battery: Engine Runtime: 27.4 h 13.
3.10 Generator Metering Menu Voltage Calibration The generator metering menu displays the generator voltage and frequency. See Figure 3-10. The voltage calibration mode can be entered from the Generator Metering menu. Contact a Kohler-authorized distributor/dealer for service. The Reset Calibration menu allows you to set the voltage reading back to the original value after calibration, if necessary. See Figure 3-10.
3.11 Generator Set Information Menu 3.12 Genset Run Time Menu The generator set model number and serial numbers are displayed. No changes are allowed from this menu. Model and serial numbers are factory set and should not require changes in the field, except in the event that the controller is being replaced. A personal computer running Kohlerr SiteTecht software is required to enter the generator set model number and serial numbers on a replacement controller.
3.13 Genset System Menu The genset system menu displays the system information shown in Figure 3-13. Generator sets are factory set and should not require changes to the system settings in the field. A Kohler-authorized distributor or dealer can adjust these settings, if necessary. If the generator set is reconnected to a different voltage or the system settings require adjustment for some other reason, see Section 3.5 for instructions to enable editing and change the system settings.
3.14 ATS Status Menu The ATS Status menu displays Model RXT transfer switch and source information. ATS menus appear if a Model RXT transfer switch is connected to the generator set. If no transfer switch is connected, or another model ATS is connected to the engine start connections, Remote ATS is displayed on the ATS Status screen. ATS ----> Status The voltage shown in these menus can be calibrated. Contact an authorized distributor or dealer for service if calibration is required.
3.15 ATS Configuration Menu Note: The ATS Configuration menu appears only if a Model RXT transfer switch is connected. Use the ATS Configuration submenu to check the Model RXT transfer switch system settings and time delays, and change the settings, if necessary. ATS ----> Configuration Normal Freq: 60.0 Hz Normal Voltage: 240.0 V Changing ATS Configuration Settings To enable editing, press the select button. The value flashes to indicate that it can be changed.
3.16 Date and Time Menu The date and time will typically be set at controller power-up. To change the date, time, or time format (12 hour or 24 hour), use the Date and Time menu. See Figure 3-16. Date and Time Date: 02Feb2018 Time: 12:34pm Time Format: 12hr|24hr <---- Return tp6810 To change the date and time, press the Select button See Figure 3-6 for instructions.
3.17 Networking Information Menus Use the networking menus to view and adjust communication settings for systems with remote RBUS devices such as a PIM or load management device, and for systems that use the Kohlerr OnCuer Plus Home Generator Management System. Networking----> Information The Networking Information menu leads to submenus for network and RBUS communication settings. Networking----> Status NS See Figure 3-18. Networking----> Configuration NC See Figure 3-19.
3.17.1 Networking Status Submenu The Networking Status submenu contains settings for OnCuer Plus. See the OnCuer Plus Software Operation Manual for information about the appropriate network settings for OnCuer Plus. Networking----> Information Networking----> Status If DHCP is enabled, IP parameters are not displayed. If DHCP is disabled (i.e., if a static IP address is used), the IP parameters are displayed. To enable or disable DHCP and change the IP settings, go to the Networking Configuration menu.
3.17.2 Networking Configuration Submenu (OnCuer Plus Password) Note: Use the OnCue password shown on the controller display for OnCue Plus applications. The networking Configuration menu includes settings used for communication with the Kohlerr OnCuer Plus Generator Management System. For the initial OnCue Plus setup, you will be required to reset the OnCue password on the RDC2 controller, and then enter it into the OnCue Plus software. To reset the password, follow the instructions in Figure 3-19.
3.17.3 RBUS Information Submenu D Model RXT transfer switch The RBUS Information menu contains settings for remote modules that communicate with the RDC2 controller using RBUS protocol.
3.17.4 Remote Devices Submenu Check the status of remote devices communicating through RBUS. Device types can include: D Model RXT ATS D Programmable interface module (PIM) D Load Shed Kit or RXT combined interface/load management board The serial numbers for the PIM and load shed kit are printed on the circuit boards. RD S/N: XXXXXXXXX <<*DeviceType*>> S/N: XXXXXXXXX <<*DeviceType*>> ... <---- Return Device Status: Connected Comm. Errors: 12345 Comm. Timeouts: 12345 ModBus ID: 12 Firmware Ver.: 1.
3.18 Programmable Interface Module (PIM) Menus The PIM status menu displays the status of inputs and outputs connected to the programmable interface module (PIM). This is a status display menu only. Input and output settings cannot be changed from the RDC2 controller’s user interface. PIM Status: PIM 1 ----> <---- Return A personal computer running Kohlerr SiteTecht software is required to change the input and output settings. Contact an authorized distributor or dealer for service.
3.19 Load Control Menus The Load Control menu displays the status of the load management inputs and outputs, and allows a test of the load management output relays. This menu appears only if a load management device is connected. Generator current is displayed as a percent of the maximum generator capacity. The load management Load ----> Control Generator Current: device adds and sheds loads based on the generator current. The test function cycles the relays in the order of their priority.
Section 4 Scheduled Maintenance 4.1 General Maintenance DANGER WARNING Hazardous voltage. Moving parts. Will cause severe injury or death. Accidental starting. Can cause severe injury or death. Disconnect the battery cables before working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery. Disabling the generator set. Accidental starting can cause severe injury or death.
The fuel system. Explosive fuel vapors can cause severe injury or death. Vaporized fuels are highly explosive. Use extreme care when handling and storing fuels. Store fuels in a well-ventilated area away from spark-producing equipment and out of the reach of children. Never add fuel to the tank while the engine is running because spilled fuel may ignite on contact with hot parts or from sparks. Do not smoke or permit flames or sparks to occur near sources of spilled fuel or fuel vapors.
Service Schedule Daily or Before Each Use Reference Check oil level and add oil if necessary. See Section 4.3 Check coolant level and add coolant if necessary. w Check for fluid leaks. See Section 4.6 Check battery connections for tightness and signs of corrosion. See Section 4.8 Check for fuel leaks, hissing, or gas odors. Weekly Check main tank supply level (LPG fuel). Check for and remove obstructions or combustible materials near exhaust outlet. See Section 4.
4.3 Lubrication System 4.3.1 4.3.3 Oil Specifications Kohler recommends KOHLERr Genuine Oil, 10W--40 or equivalent. KOHLERr Genuine Oil is fully synthetic and engineered specifically for gaseous-fueled (NG/LPG) engines requiring SAE 10W--40 oil. Note: The oil must meet the specifications for zinc, phospohorous, and ash content shown in Figure 4-1. Oil Additions Adding some oil between oil changes is normal. The amount varies with generator set usage.
4. Check for leaks. Oil Change Procedure Whenever possible, drain the oil while it is still warm. a. Press the OFF button on the RDC2 generator set controller. 1. Drain the oil. a. Press the OFF button on the RDC2 generator set controller. b. Disconnect the power for the battery charger. c. Disconnect the generator set engine starting battery, negative (--) lead first. b. Reconnect the generator set engine starting battery, negative (--) lead last. c. Reconnect the power for the battery charger. d.
4.4 Air Cleaner WARNING Air Cleaner Service Procedure A dry-type air cleaner silences and filters the intake air. See Figure 4-4. The air intake silencer assembly connects to the intake manifold via a rubber hose. Accidental starting. Can cause severe injury or death. Disconnect the battery cables before working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery. Disabling the generator set.
4.5 Exhaust System CAUTION WARNING Carbon monoxide. Can cause severe fainting, or death. Hazardous noise. Can cause hearing loss. nausea, DO NOT locate the generator set near patios, decks, play areas, or animal shelters. Generator set operation. Carbon monoxide can cause severe nausea, fainting, or death. Carbon monoxide is an odorless, colorless, tasteless, nonirritating gas that can cause death if inhaled for even a short time. Avoid breathing exhaust fumes when working on or near the generator set.
4.6 Cooling System WARNING 4.6.2 Cooling System Inspection To prevent generator shutdown or damage because of overheating: D Keep the cooling air inlets clean and unobstructed D Inspect the radiator’s exterior for obstructions and Hot coolant and steam. Can cause severe injury or death. remove dirt and foreign material with a soft brush or cloth to avoid damaging the radiator fins. Before removing the pressure cap, stop the generator set and allow it to cool.
4.6.4 Flushing and Cleaning For optimum protection, drain, flush, and refill the cooling system at the interval listed in the service schedule. 4.7 Spark Plugs WARNING Flushing and Cleaning Procedure 1. Flush the system with clean water. 2. Drain, clean, and flush the coolant overflow bottle. 3. Refill the cooling system as instructed in Section 4.6.5. 4.6.5 Filling Cooling System Coolant Capacity, L (gal.) Generator Set 20.8 (5.5) Generator Set with Block Heater 21.4 (5.
Note: Do not sandblast, wire brush, scrape, or otherwise service spark plugs in poor condition. Obtain a new plug for best results. 9. Check the spark plug gap before installing any spark plug. See Figure 4-7 and Figure 4-8. Attain a correct gap when the feeler (or wire) passes between the spark plug electrode. It should pass easily but with some resistance or drag; otherwise adjust as necessary. Spark Plug Specifications Spark plug gap 0.76 mm (0.03 in.) Spark plug torque 27 Nm (20 ft. lbs.
Problem/Condition Means of Identification Possible Cause/Solution Gap-bridged spark plug Built-up deposits and gap between electrodes closing. Oil or carbon fouling. Clean and regap the spark plug. Oil-fouled spark plug Wet, black deposits on the insulator shell, bore, and electrodes. Excessive oil entering combustion chamber through worn rings and pistons, excessive clearance between valve guides and stems, or worn or loose bearings. Replace the spark plug.
4.8 Battery Consult the battery manufacturer’s instructions regarding battery care and maintenance. WARNING Sulfuric acid in batteries. Can cause severe injury or death. Wear protective goggles and clothing. Battery acid may cause blindness and burn skin. Battery electrolyte is a diluted sulfuric acid. Battery acid can cause severe injury or death. Battery acid can cause blindness and burn skin. Always wear splashproof safety goggles, rubber gloves, and boots when servicing the battery.
4.8.1 Checking Electrolyte Level Check the electrolyte level of batteries with filler caps monthly. Remove filler caps and verify that electrolyte level reaches bottom of filler holes. Refill as necessary with distilled water. DO NOT add fresh electrolyte. Tighten all filler caps. If water is added during freezing temperatures, run the generator set for 20--30 minutes to mix the electrolyte and water to prevent battery damage from freezing. 4.8.
4.9 Storage Procedure 5. Keep spark plugs in their holes or seal spark plug holes with suitable threaded metal plugs. WARNING 6. Clean the exterior of the generator set and spread a light film of oil or silicon spray over any exposed surfaces that may be subject to rust or corrosion. 7. Seal the air inlet, exhaust pipe, and fuel tank cap with tape. Hot engine and exhaust system. Can cause severe injury or death. 8. Disconnect and remove the battery.
Section 5 Troubleshooting 5.1 Introduction Use the troubleshooting charts in this section to diagnose and correct common problems. First check for simple causes such as a dead engine starting battery, loose connections, or an open circuit breaker. The charts include a list of common problems, possible causes of the problem, and recommended corrective actions. If the procedures in this manual do not explain how to correct the problem, contact an authorized Kohler distributor/dealer.
5.5 Generator Set Troubleshooting Figure 5-1 contains generator set troubleshooting, diagnostic, and repair information. Check for loose connections before replacing parts. Note: Read all safety precautions at the beginning of this publication before performing any work on the generator set. Problem The generator set does not crank. Possible Cause Battery weak or dead. Battery connections reversed or poor. Blown fuse(s). Corrective Action Recharge or replace the battery. Check the connections.
5.6 Controller Troubleshooting Figure 5-2 contains basic troubleshooting information for the RDC2 controller. Problem Possible Cause Corrective Action Controller LCD display is off. Low or no battery voltage. Check connections. Check generator set battery. See Figure 5-1. Controller display backlight is off. Backlight turns off after about 1 minute with no activity. Backlight will turn on when a button is pressed or the generator set starts.
Notes 66 Section 5 Troubleshooting TP-7102 4/18
Appendix A Abbreviations The following list contains abbreviations that may appear in this publication. A, amp ABDC AC A/D ADC adj. ADV Ah AHWT AISI ALOP alt. Al ANSI AO APDC API approx. APU AQMD AR AS ASE ASME assy. ASTM ATDC ATS auto. aux. avg. AVR AWG AWM bat. BBDC BC BCA BCI BDC BHP blk. blk. htr. BMEP bps br. BTDC Btu Btu/min. C cal. CAN CARB CAT5 CB CC cc CCA ccw. CEC cert.
kg/cm2 kilograms per square centimeter kgm kilogram-meter kg/m3 kilograms per cubic meter kHz kilohertz kJ kilojoule km kilometer kOhm, k kilo-ohm kPa kilopascal kph kilometers per hour kV kilovolt kVA kilovolt ampere kVAR kilovolt ampere reactive kW kilowatt kWh kilowatt-hour kWm kilowatt mechanical kWth kilowatt-thermal L liter LAN local area network L x W x H length by width by height lb.
Notes TP-7102 4/18 69
Notes 70 TP-7102 4/18