Install Drawing

Table Of Contents
6
7
8
C
D
1
2
34
56
7
8
A
B
C
D
1
2
3
4
5
A
B
HTS OF DESIGN OR INVENTION ARE RESERVED.EXCEPT IN CONNECTION WITH KOHLER CO. WORK. ALL RIG THIS DRAWING IN DESIGN AND DETAIL IS KOHLER CO. PROPERTY AND MUST NOT BE USED
KOHLER, WISCONSIN 53044
SURFACE FINISH
MAX.
UNLESS OTHERWISE SPECIFIED:
ALL DIMENSIONS IN MILLIMETERS
GENERAL TOLERANCES:
X.XX
0.25
X.X
1.0
X
1.5
ANGLES
0 30'
REV DATE
CHANGE
NUMBER
ON COMPOSITE DWGS, SEE PART NO. FOR REVISION LEVEL
INDICATES PART NUMBERS AFFECTED BY LATEST
DRAWING REVISION
BY
- 27JAN2021 CT209473 NEW DRAWING RVM
DO NOT SCALE.
THIS ASSEMBLY OR PART MUST
COMPLY WITH PEP-RML-001.
REFERENCE CAD MODEL FOR
UNSPECIFIED DIMENSIONS.
SCALE: 0.050
SHEET SIZE: B
SHEET 2 OF 2
TITLE:
DIMENSION PRINT,
48RCLC/60RCLB
DWG NO.: ADV-9760
THIRD ANGLE PROJECTION
=MAJOR
0
=CRITICAL
0
CHARACTERISTICS COMPLY WITH
KPS-80022
DRAWN
BY
RVM
DATE:
APPROVED
BY
TAS 27JAN2021
OCCUPIED STRUCTURE
OCCUPIED STRUCTURE
OCCUPIED STRUCTURE
OCCUPIED STRUCTURE
SET
SET
SET
SET
SERVICE SIDE
DOOR
SERVICE
SIDE DOOR
SERVICE SIDE
DOOR
SEE NOTE 7
SEE NOTE 7
SEE NOTE 7
SEE NOTE 7
SERVICE SIDE DOOR
48 RCLC/ 60 RCLB
SEE NOTE 8
SEE NOTE 8
INSTALLATION GUIDELINES
1) EXHAUST IS AIMED AWAY FROM OR PARALLEL TO THE STRUCTURE.
2) EXHAUST IS NOT DIRECTED AT PLAY AREAS, PATIOS OR OTHER
AREAS WHERE PEOPLE CONGREGATE.
3) THE NEAREST WINDOW, VENT, DOOR OR SIMILAR STRUCTURE
OPENING IS AT LEAST 5 FEET FROM THE EXHAUST END OF THE GENERATOR.
4) GENERATOR SET MUST BE INSTALLED A MINIMUM OF 18 INCHES FROM STRUCTURE
PER NFPA 37, HOWEVER, ACTUAL DISTANCE MAY DIFFER BASED ON STATE AND LOCAL CODES.
5) WINDOWS & DOORS ON ADJACENT WALLS ARE CLOSED.
6) FURNACE AND OTHER SIMILAR INTAKES ARE AT LEAST 10 FEET FROM
EXHAUST END OF GENERATOR.
7) 4" THICK CONCRETE PAD EXTENDING 6" BEYOND GENSET ON ALL SIDES.
8) NO PLANTS, SHRUBS OR OTHER COMBUSTIBLES ALLOWED IN
CLEARANCE AREA. (MINIMUM 8 FT. FROM EXHAUST END).
9) SENSITIVE PLANTS, PATIO FURNITURE, ETC. ARE AT LEAST 8 FEET FROM
EXHAUST END OF SET.
10) REFER TO OWNERS MANUAL FOR OTHER INSTALLATION CONSTRAINTS.
SEE NOTE 8
SEE NOTE 8
SEE NOTE
SEE NOTE
SEE NOTE
SEE NOTE