2.4.4 Engine Cooldown
The engine cooldown time delay allows the engine to run after the loads have been removed.
The engine cooldown time delay is set to 5 minutes. The engine stops before the cooldown time delay expires if the temperature
drops below the cooled-down temperature level, or if the temperature rises above the high limit during the cooldown cycle.
2.4.5 Automatic Operation
The 6VSG monitors the voltage of a storage battery bank connected to (+) and () of the output block to determine charge
condition of the storage battery (see Figure 10).
If the storage battery voltage falls below the minimum voltage for more than 3 minutes, or if a remote start command is received,
the generator set starts. A remote start command can be activated by closing the remote start contacts across 3 and 4 or by a
start exercise command.
When the generator set load falls below the minimum % load for more than 3 minutes, or a remote stop command is received,
the generator set stops. A remote stop command can be caused by opening the remote start contacts across 3 and 4 or by the
exercise time ending.
The minimum voltage, minimum load, and time delays are adjustable using a personal computer and Kohler
®
SiteTech™
software. Contact your Kohler distributor.