Figure 27 Effect of Changing the System Voltage Setting
Auto Start Volt: The 6VSG will automatically start when the battery bank voltage has reached or fallen below this value for 180
seconds (3 minutes). Default settings are shown in Figure 28.
Nominal Voltage
24V
36V
48V
Default System Voltage, VDC
25
37.5
50
Figure 28 Auto Start Voltage
Note:
The 3-minute (180-second) time delay can be changed using a personal computer (laptop) and Kohler
®
SiteTech™ software.
Contact a Kohler authorized distributor or dealer to adjust the delay setting, if necessary.
Auto Stop Load: The auto stop load is set as a percentage of full load. As the battery bank approaches the fully charged state,
the charge rate slows, and the load on the generator set decreases. The 6VSG will automatically stop when the load has reached
or fallen below the Auto Stop Load setting for 180 seconds (3 minutes). The default setting is 40% load.
Load Limit (%): This setting limits the current output to the maximum charge rate specified by the battery manufacturer or load
in the application. The default setting is 100%, which gives the maximum current values shown in Figure 29. Refer to the battery
manufacturer's recommended maximum charge rate and contact an authorized Kohler distributor or dealer if the setting needs
to be changed.
𝐋𝐨𝐚𝐝 𝐋𝐢𝐦𝐢𝐭 =
(𝐑𝐞𝐜𝐨𝐦𝐦𝐞𝐧𝐝𝐞𝐝 𝐜𝐡𝐚𝐫𝐠𝐢𝐧𝐠 𝐯𝐨𝐥𝐭𝐚𝐠𝐞 (𝐕𝐃𝐂) 𝐱 𝐌𝐚𝐱𝐢𝐦𝐮𝐦 𝐜𝐡𝐚𝐫𝐠𝐢𝐧𝐠 𝐜𝐮𝐫𝐫𝐞𝐧𝐭 (𝐚𝐦𝐩𝐬)) 𝐱 𝟏𝟎𝟎
𝟔𝟎𝟎𝟎 𝐰𝐚𝐭𝐭𝐬
Nominal Voltage
24V
36V
48V
System Voltage, VDC
27
40.5
54
Maximum Current at 100% Load Limit, Amps
222
148
111
Figure 29 Maximum Charge Current at Default Load Limit Setting of 100%