Spec Sheet
Models: 6VSG
Natural Gas/LPG
The Kohler
r
Advantage
D High Quality DC Power
d 6 kW DC generator designed specifically for renewable
energy applications and other remote applications
d Provides consistent DC output to maintain battery banks
directly without inefficient conversions from alternating
current
d Can be used for industrial battery bus support to reduce
thesizeofbatterybanks
D Quiet and Economical
d Variable speed helps to keep noise low and reduce fuel
consumption as compared to fixed-speed AC
generators
d Generator can maintain batteries directly without the
need for an expensive converter or monitoring
equipment
D Flexible
d Generator senses when battery bank is running low and
automatically turns on to maintain batteries when
renewable energy sources cannot keep up with demand
d Generator can also be set up to turn on when the
renewable system’s inverter sends a signal
d Compatible with positive or negative grounded systems
d 24, 36, and 48 volt configurations
D Reliable
d 18-month/1000-hour warranty for off-grid applications
d 5-year/2000-hour warranty for on-grid applications
24/36/48 VDC
G4- 213 (6VSG) 1/22f
Standard Features
D VSC Controller
d Electronic speed control responds quickly to varying
demand
d Backlit LCD display with adjustable contrast is easy to
read in direct sunlight or low light
D Certifications
d Meets applicable U.S. Environmental Protection Agency
(EPA) emissions regulations for all 50 states, for both LPG
and natural gas *
d UL 2200 listed
d CSA certified
D Standard Features
d OnCuer Plus Generator Management System: allows
remote monitoring and control of the generator from
anywhere in the world
d Kohler PRO 10W- 50 synthetic oil extends oil change
intervals to 300 hours
D Optional Accessories Available
d Programmable Interface Module (PIM): provides 2 inputs
and 6 outputs for custom control of circuits (available only
if communications kit is not installed)
d Oil Make-Up Kit: extends the time between oil level
checks to 24 hours
D Optional Communications Kit Available
d Factory-installed inside the generator set
d Enclosure intrusion alarm
d Low fuel pressure switch
d Interface board with 2 inputs and 6 outputs
d Factory-programmed inputs and outputs:
Input 1: Fuel Pressure Low Warning
Input 2: Enclosure Intrusion Alarm
Output 1: Run
Output 2: Common Fault
Output 3: Battery Voltage Low
Output 4: Fuel Pressure Low Warning
Output 5: Enclosure Intrusion Alarm Warning
Output 6: Reserve Oil Empty (oil makeup kit required)
* As a stationary generator set powered by a spark-ignited engine, this
product is not required to meet CARB-specific off-road engine
regulations.
Generator Ratings
Model
Nominal
Voltage
VDC
Output
Voltage
VDC
Ratings
Natural Gas and LPG
kW Amps
6VSG
24 27 6 223
36 40.5 6 149
48 54 6 112
RATINGS: Ratings are in accordance with ISO- 3046/1, BS5514, AS2789, and DIN 6271.
GENERAL GUIDELINES FOR DERATING: ALTITUDE: Derate 4% per 305 m (1000 ft.)
elevation above 915 m (3000 ft.). TEMPERATURE: Rated at 6 kW for the entire operating
range, - 29 to 49_C(-20to120_F).
Availability is subject to change without notice. The generator set manufacturer reserves the
right to change the design or specifications without notice and without any obligation or liability
whatsoever.