Spec Sheet

G4- 213 (6VSG) 1/22f
Fuel Pipe Size
Minimum Gas Pipe Size Recommendation, in. NPT
Pipe Length,
m(ft.)
Natural Gas
115,000 Btu/hr.
LPG
106,000 Btu/hr.
8 (25)
3/4 1/2
15 (50) 1 3/4
30 (100) 1 3/4
46 (150) 1 3/4
61 (200) 1 1
Fuel Requirements
Fuel System 6VSG
Fuel types Natural Gas or LPG
Fuel supply inlet 1/2 NPT
Fuel supply pressure, kPa (in. H
2
O):
Natural gas 1.2- 2.7 (5-1 1)
LPG 1.7- 2.7 (7-11)
Fuel Composit ion Limits *
Nat. Gas LPG
Methane, % by volume (minimum) 90 min.
Ethane, % by volume (maximum) 4.0 m ax.
Propane, % by volume 1.0 max. 85 min.
Propene, % by volume (maximum) 0.1 max. 5.0 max.
C
4
and higher, % by volume 0.3 max. 2.5 max.
Sulfur, ppm mass (maximum) 25 max.
Lower heating value,
MJ/m
3
(Btu/ft
3
), min.
33.2 (890) 84.2 (2260)
* Contact your local distributor for suitability and rating derates based
on fuel compositions outside these limits.
Operation Requirements
Fuel Consumption
Model Fuel Type %Load
Fuel Consumption,
m
3
/hr. (cfh)
6VSG
Natural Gas
100
3.3 (116)
75
2.7 (96)
50
2.1 (75)
25
1.8 (62)
LPG
100
1.2 (42)
75
1.0 (35)
50
0.9 (32)
25
0.7 (27)
Nominal fuel rating: Natural gas: 37 MJ/m
3
(1000 Btu/ft.
3
)
LPG: 93 MJ/m
3
(2500 Btu/ft.
3
)
LPG conversion factors: 8.58 ft.
3
=1lb.
0.535 m
3
=1kg
36.39 ft.
3
=1gal.
Sound Data
All sound levels are measured at 7 meters.
Sound Levels at 7 m (23 ft.)
Load Average dB(A) Single Point dB(A)*
No load 59 57
50% 62 59
100% 66 62
* Compared to competitor ratings. Lowest of 8 points measured around
the generator. Sound levels at other points around generator may be
higher depending on installation parameters.
VSC Controller
Voltage: 54 V
Load: 80%
The VSC controller provides integrated control for the 6VSG
generator set and programmable interface module (PIM) or
communications kit.
The VSC controller’s LCD screen displays status messages and
system settings that are clear and easy to read in direct sunlight
or low light.
VSC Controller Features
D Membrane keypad
d OFF, AUTO, and RUN pushbuttons
d Select and arrow buttons for access to system
configuration and adjustment menus
D LED indicators for OFF, AUTO, and RUN modes
D LED indicators for % load readings
D LCD display
d Two lines x 16 characters per line
d Backlit display with adjustable contrast for excellent
visibility in all lighting conditions
D Scrolling system status display
d Generator set status
d Voltage and % load
d Engine temperature
d Oil pressure status
d Engine starting battery voltage
d Engine runtime hours
D Date and time displays
D Smart engine cooldown senses engine temperature
D Variable speed maintains fixed DC voltage with varying load
D User-adjustable low battery limit
D System settings
d System voltage (DC)
d Voltage calibration
d Auto start battery bank voltage limit
d Auto stop output current
d System current limit
D Automatic start with programmed cranking cycle
D Remote two-wire start/stop capability for optional connection
to a third-party inverter
D Programmable exerciser can be set to start automatically on
any future day and time and run every week or every two
weeks
D Front-access mini USB connector for SiteTecht connection
D Integral Ethernet connector for Kohlerr OnCuer system
D Built-in 2.5 amp battery charger for engine starting battery
(powered by 120 VAC, 50/60 Hz source)