Spec Sheet

Models:
14RCA(L)
Multi-Fuel
LPG/Natural Gas
Standard Features
RDC2 Controller
One digital controller manages both the generator set and
transfer switch functions (with optional Model RXT).
Electronic speed control responds quickly to varying
demand.
OnCue Plus Generator Management System for remote
monitoring is included with the generator.
Kohler Command PRO Engine Features
Kohler Command PRO OHV engine with hydraulic valve
lifters for reliable performance without routine valve
adjustment or lengthy break-in requirements.
Designed for Easy Installation
Sturdy aluminum base can be mounted on gravel or a
concrete mounting pad.
Fuel and electrical connections through the enclosure wall
eliminate the need for stub-ups through the base.
Customer connection terminal block located near the
controller allows easy access for field wiring.
Designed for outdoor installation only.
Certifications
Meets emission regulations for U.S. Environmental
Protection Agency (EPA) with both natural gas and LPG.
UL 2200/cUL listed (60 Hz model).
CSA certification available (60 Hz model).
Accepted by the Massachusetts Board of Registration of
Plumbers and Gas Fitters.
Meets 181 mph wind rating.
14RCAL models packaged with a Model RXT automatic
transfer switch are available. See page 4 and the Model
RXT ATS specification sheet.
Warranty
5-year/2000 hour limited warranty for on-grid (standby)
applications in locations served by a reliable utility source.
18 month / 1000 hour limited warranty for off-grid
(non-standby) applications.
The Kohler
Advantage
High Quality Power
Kohler home generators provide advanced voltage and
frequency regulation along with ultra-low levels of
harmonic distortion for excellent generator power quality to
protect your valuable electronics.
Extraordinary Reliability
Kohler is known for extraordinary reliability and
performance and backs that up with a premium 5-year or
2000 hour limited warranty.
Powerful Performance
Exclusive Powerboost technology provides excellent
starting power. The Kohler 14 kW generator can easily
start and run a 5 ton air conditioner.
Aluminum Enclosure
Attractive aluminum enclosure allows installation as
close as 18 inches from your home or small business.
Enclosure panels can be removed without tools to allow
easy access for maintenance and service.
Check the appliance manufacturer’s specifications for actual power requirements. Consult a Kohler Power Systems professional to calculate your exact residential power system requirements.
Meets NFPA guidelines for 18 inch clearance to combustible materials. Check state and local codes for minimum distance required from a structure.
G4-270 (14RCA) 5 /2 1d
Generator Ratings
Standby Ratings Non-Standby Ratings
Line Circuit
Breaker
Natural Gas LPG Natural Gas LPG
Alt. Voltage Phases Hz
kW/
kVA
Amps kW/kVA Amps
kW/
kVA
Amps
kW/
kVA
Amps Amps Poles
2F5 120/240 1 60 12/12 50 14/14 58 12/12 50 14/14 58 70 2
2G5
120/208 3 60 12/15 41 13/16 45 12/15 41 13/16 45 50 3
120/240 3 60 12/15 36 13/16 39 12/15 36 13/16 39 50 3
277/480 3 60 12/15 18 13/16 20 12/15 18 13/16 20 25 3
Note: The line circuit breaker is automatically selected based on the generator set model and voltage configuration.
RATINGS: Standby ratings apply to installations served by a reliable utility source. All single-phase units are rated at 1.0 power factor. The standby rating is applicable to variable loads with an average
load factor of 80% for the duration of the power outage. No overload capacity is specified at this rating. Ratings are in accordance with ISO- 3046/1, BS5514, AS2789, and DIN 6271. GENERAL
GUIDELINES FOR DERATING: ALTITUDE: Derate 4% per 305 m (1000 ft.) elevation above 153 m (500 ft.). TEMPERATURE: Derate 2% per 5.5C (10F) temperature increase above 16C (60F).
Availability is subject to change without notice. The generator set manufacturer reserves the right to change the design or specifications without notice and without any obligation or liability whatsoever.
Contact your local Kohler Co. generator distributor for availability.

Summary of content (4 pages)