Load Shed Spec Sheet

© 2013 by Kohler Co. All rights reserved.
DISTRIBUTED BY:
G11-124 (Load Shed Ki t for RXT/RDT) 6/13
Operation
D Loads are automatically added or disconnected based on generator capacity.
D The Kohler-patented load control system uses dynamic logic to prevent shedding important loads unnecessarily when air
conditioning, refrigerator, or water pump motors start.
D The load shed kit and generator communicate to provide smart power management. The time to shed loads decreases as each
load is shed to quickly adapt to critical power requirements.
D Load shed power level and frequency setpoint adjustments are possible only by using Kohlerr SiteTecht software, available to
Kohler-authorized distributors and dealers.
Specifications
Connection Rating Connection
Pilot Relays* and HVAC Relays (qty. 2)
125VAC, 10 A (general purpose)
120VAC, 125VA (pilot duty)
Connect to #6 screw on terminal block
RBUS Communication and Power
Connections to the RDC2/DC2 controller
0.5A@12VDC
Use Belden #9402 or equivalent 20 AWG
shielded, twisted-pair communications cable
[
* Four (4) pilot relays are provided for customer-supplied load-switching contactors/relays.
[ For long distances, use an equivalent shielded, twisted pair cable for RBUS connections and individual 12--20 AWG wires (qty . 2) for power
connections. A communication harness for the Model RXT transfer switch is included with the load shed kit. See TT--1609, Load Shed Kit
Installation Instructions, for details.
Location Inside ATS Enclosure
1
1. Typical location of load shed kit. Location varies with transfer
switch model. (cover removed for illustration)
Current Transformer
The load shed kit includes a current transfomer (CT) for
load monitoring. If the application requires cables that are
too large for the inner diameter (I.D.) of the CT provided,
order current transformer GM17250, or obtain a CT that
meets the specifications shown below.
CT Specifications
GM83929
(provided)
GM17250 *
Primary Rating 400 Amps 400 Amps
Secondary Rating 3VAC 3VAC
Burden Resistor 16 Ohms 16 Ohms
Burden Resistor
Location
Internal Internal
Inner Diameter (I.D.) 28.7 mm (1.13 in.) 57.2 mm (2.25 in.)
* Order GM17250 for applications that use larger cables.
Kohler Power Systems
Asia Pacific Headquarters
7 Jurong Pier Road
Singapore 619159
Phone (65) 6264-6422, Fax (65) 6264-6455
KOHLER CO., Kohler, Wisconsin 53044 USA
Phone 920-457-4441, Fax 920-459-1646
For the nearest sales and service outlet in the
US and Canada, phone 1-800-544-2444
KOHLERPower.com
Availability is subject to change without notice. Kohler Co. reserves the
right to change the design or specifications without notice and without any
obligation or liability whatsoever. Contact your local Kohlerr generator
distributor for availability.