Load Shed Spec Sheet

Transfer Switch Accessories
Applicable Models
D RXT Automatic Transfer Switch (without load center)
D RDT Automatic Transfer Switch (without load center)
D RDT 200 amp service entrance rated transfer switch with
42-circuit load center
D A Kohlerr single-phase generator set equipped with the
RDC2 or DC2 controller is required. The load shed kit
operates with the following generator set models: *
d 14RESA and 14RESAL
d 20RESA and 20RESAL
d 38RCL
d 48RCL
Standard Features
D Automatically manages up to six residential loads:
d Four customer-provided power relays can be
connected for management of non-essential
secondary loads.
d Two HVAC relays to control two independent air
conditioner loads are included.
D Current transformer for load monitoring is provided.
D The load shed kit mounts inside the enclosure on Kohlerr
Model RXT and RDT automatic transfer switches.
Load Management
D The load shed kit disconnects non-critical loads to
prevent generator overload, in compliance with NEC
2008.
D The load shed kit monitors generator current and
frequency to determine when to shed loads. This
monitoring prevents frequency drops that can damage
valuable electronics like computers and televisions.
D Load management with the load shed kit allows the use
of a smaller generator set.
Priority Setting
D Loads are added and shed according to their priority. Load
1 is the top priority, which is added firstand shed last. Load
6 is the lowest priority.
D Less critical loads can be turned off automatically when
essential appliances are running.
D Load priorities are hard-wired at installation.
* Information available at time of publication.
Load Shed Kit
Load Shed Assembly
G11-124 (Load Shed Ki t for RXT/RDT) 6/13