Dimensions Guide

1-1/2"
Notes
Required Electrical Service
Measure your actual product for rough-in details.
Two dedicated circuits required, protected with Class A
Ground-Fault Circuit-Interrupter (GFCI). Outside North America,
this device may be known as a Residual Current Device (RCD).
Install this product according to the installation
instructions.
The hot water supply should be 70% of the
capacity of the bath or greater. Installations will
vary.
120 V, 15 A, 60 HzBlower:
120 V, 15 A, 60 HzAir bath:
Technical Information
Provide one grounded electrical outlet within 24"
(610 mm) of each component.
All product dimensions are nominal.
Three-wall alcoveInstallation:
Remote blower installation kit K-1446 is available
for relocating the blower. Provide access for
servicing the blower.
RightDrain location:
47-1/8" x 19-11/16" (1197 mm x 500 mm)Basin area, bottom:
Do not relocate or alter the PVC tee or coiled
flexible tubing connected to the blower. Follow
the blower relocation instructions exactly.
61-7/16" x 26" (1561 mm x 660 mm)Basin area, top:
115 lbs (52.2 kg)Weight:
56 lbs/ft² (273.4 kg/m²)Minimum floor load:
13-5/8" (346 mm)Water depth:
67 gal (253.6 L)Water capacity:
Blower: 120 V, 10 A, 60 Hz
Air bath: 120 V, 5 A, 60 Hz
Electrical component
rating:
1-15/16" (49 mm)Minimum flat for door:
1-800-4KOHLER (1-800-456-4537)
Kohler Co. reserves the right to make revisions without notice to product specifications.
For the most current Specification Sheet, go to www.kohler.com.
9-7-2019 06:15 - US
Mariposa
®
integral apron Heated BubbleMassage
air bath
K-1224-GHRA