Product Card

KD200
Engine type
Alternator type
Performance class
6068HF120-183
KH01100T
G3
GENERAL CHARACTERISTICS
Frequency (Hz)
Voltage (V)
Standard control panel
Optional control panel
Optional control panel
POWER
ESP
PRP
Voltage
kWe
kVA
kWe
Standby Amps
DIMENSIONS COMPACT VERSION
Length (mm)
2370
Width (mm)
1114
Height (mm)
1480
Dry weight (kg)
1716
Tank capacity (L)
340
DIMENSIONS SOUNDPROOFED VERSION
Commercial reference of the enclosure
M226
3508
1200
1830
2306
340
76
Length (mm)
Width (mm)
Height (mm)
Dry weight (kg)
Tank capacity (L)
Acoustic pressure level @1m in dB(A)
Sound power level guaranteed (Lwa)
Acoustic pressure level @7m in dB(A)
95
POWER DEFINITION
PRP : Prime Power is available for an unlimited number of annual
operating hours in variable load applications, in accordance with ISO
8528-1. ESP : The standby power rating is applicable for supplying
emergency power in variable load applications in accordance with ISO
8528-1. Overload is not allowed
TERMS OF USE
According to the standard, the nominal power assigned by the genset is
given for 25°C Air Intlet Temperature, of a barometric pressure of 100
kPA (100 m A.S.L), and 30 % relative humidity. For particular conditions
in your installation, refer to the derating table.
ASSOCIATED UNCERTAINTY
For the generator sets used indoor, where the acoustic pressure levels
depend on the installation conditions, it is not possible to specify the
ambient noise level in the operating and maintenance instructions.
You will also find in our operating and maintenance instructions a
warning concerning the air noise dangers and the need to implement
appropriate preventive measures.
This document is not contractual - Kohler Co. reserves the right to modify any of the characteristics without notice, in a constant effort to improve the quality of its products.
GBD5-03010 (KD200) 03/17
50
400/230
APM303
DEC4000
M80
DESCRIPTIVE
Kohler Co. Provides one-source responsibility for the
generating system and accessories
The generator set and its components are prototype-
tested, factory-built, and production-tested
A one-year limited warranty covers all systems and
components
Mechanic governor
Mechanically welded chassis with antivibration
suspension
Main line circuit breaker
Radiator for core temperature of 48/50°C max with
mechanical fan
Protective grille for fan and rotating parts (CE option)
9 dB(A) silencer supplied separately
Charger DC starting battery with electrolyte
12 V charge alternator and starter
Delivered with oil and coolant -30°C
Manual for use and installation
65
415/240 160 200 146 182 278
400/230 160 200 146 182 289
380/220 160 200 146 182 304
200/115 160 200 146 182 577
240 TRI 160 200 146 182 481
230 TRI 160 200 146 182 502
220 TRI 160 200 146 182 525
220/127 144 180 131 164 472

Summary of content (5 pages)