Product Card

KD44
Engine type
3029TFS29
Alternator type KH00500T
Performance class
G3
GENERAL CHARACTERISTICS
Frequency (Hz)
Voltage (V)
Standard control panel
Optional control panel
Optional control panel
POWER
ESP
PRP
Voltage
kWe
kVA
Standby Amps
200/115 35 44 32 40 127
240 TRI 35 44 32 40 106
230 TRI 35 44 32 40 110
220 TRI 35 44 32 40 115
DIMENSIONS COMPACT VERSION
Length (mm)
1700
Width (mm)
896
Height (mm)
1221
Dry weight (kg)
820
Tank capacity (L)
100
DIMENSIONS SOUNDPROOFED VERSION
Commercial reference of the enclosure M127
Length (mm) 2080
Width (mm) 960
Height (mm) 1415
Dry weight (kg) 1040
Tank capacity (L) 100
Acoustic pressure level @1m in dB(A) 74
Sound power level guaranteed (Lwa) 91
DESCRIPTIVE
Kohler Co. Provides one-source responsibility for the
generating system and accessories
The generator set and its components are prototype-
tested, factory-built, and production-tested
A one-year limited warranty covers all systems and
components
POWER DEFINITION
PRP : Prime Power is available for an unlimited number of annual
operating hours in variable load applications, in accordance with ISO
8528-1. ESP : The standby power rating is applicable for supplying
emergency power in variable load applications in accordance with ISO
8528-1. Overload is not allowed
TERMS OF USE
According to the standard, the nominal power assigned by the genset is
given for 25°C Air Intlet Temperature, of a barometric pressure of 100
kPA (100 m A.S.L), and 30 % relative humidity. For particular conditions
in your installation, refer to the derating table.
ASSOCIATED UNCERTAINTY
For the generator sets used indoor, where the acoustic pressure levels
depend on the installation conditions, it is not possible to specify the
ambient noise level in the operating and maintenance instructions.
You will also find in our operating and maintenance instructions a
warning concerning the air noise dangers and the need to implement
appropriate preventive measures.
This document is not contractual - Kohler Co. reserves the right to modify any of the characteristics without notice, in a constant effort to improve the quality of its products.
GBD5-03003 (KD44) 03/17
Acoustic pressure level @7m in dB(A) 62
50
400/230
APM303
DEC4000
M80
Mechanic governor
Mechanically welded chassis with antivibration
suspension
Main line circuit breaker
Radiator for core temperature of
48/50°C max with
mechanical fan
Protective grille for fan and rotating parts (CE option)
9 dB(A) silencer supplied separately
Charger DC starting battery with electrolyte
12
V charge alternator and starter
Delivered with oil and coolant -30°C
Manual for use and installation
415/240 35 44 32 40 61
400/230 35 44 32 40 64
380/220 34 43 31.2
39
65