Spec Sheet

Automatic Transfer Switches
Service Entrance Rated
Model: KEP
Transfer Switch Standard Features
Enclosed Contact Power Switching Units
D Service entrance automatic transfer switches incorporate an
isolating mechanism and overcurrent protection on the utility supply,
eliminating the need to have a separate, upstream utility source
circuit breaker/disconnect switch.
D UL 1008 listed, file #58962
D IBC seismic certification available
D Fully enclosed silver alloy contacts provide high withstand rating.
D 3-cycle short circuit current withstand-tested in accordance with
UL 1008
D Completely separate utility and generator set power switching units
provide redundancy (no common parts) and are easy to service.
D Utility disconnect power switching units have overcurrent protection;
generator disconnect is available with or without overcurrent
protection:
d Molded case circuit breakers (MCCB) include thermal-magnetic
or electronic trip overcurrent protection
(80% rated).
d Molded case switches (MCSW) do not include overcurrent
protection (100% rated) (available on generator disconnect only).
d Insulated case circuit breakers (ICCB) include electronic trip
overcurrent protection (100% rated).
d Insulated case switches (ICSW) do not include overcurrent
protection (100% rated) (available on generator disconnect
only).
D Inherent stored-energy design prevents damage if manually
switched while in service.
D Heavy duty brushless gear motor and operating mechanism provide
mechanical interlocking and extreme long life with minimal
maintenance.
D Safe manual operation permits easy operation even under adverse
conditions.
D All mechanical and control devices are visible and readily
accessible.
D Padlockable service disconnect control switch
D Status indicators
D Two-position control circuit isolation switch disconnects utility power
to the transfer switch c ontroller.
D Load shed (Forced transfer from Emergency to OFF).
(Customer-supplied signal [contact closure] is required for the
forced transfer to OFF function.)
D NEMA 1, 3R, 4X and 12 enclosures are available.
Service Disco nnect Switch
D Service disconnect to OFF position
D Two-position switch with padlockable cover disconnects the normal
and emergency sources.
D Controller display shows Service Disconnected and the NOT IN
AUTO LED flashes.
D Lamp illuminates to indicate that the switch is in the DISCONNECT
position.
G11-141 (Model KEP Service Entrance Rated Transfer Switch) 1/18d Page 1
Controller
D Decision-Makerr MPAC 1500
Ratings
Power
Switching
Device
Current
Voltage,
Frequency
Molded case
(MCCB)
200 208--240 VAC
60 Hz
100--1200 208--480 VAC
60 Hz
Insulated Case
(ICCB)
800--4000
208--480 VAC,
60 Hz