Spec Sheet

G11-141 (Model KEP Service Entrance Rated Transfer Switch) 1/18d Page 3
Cable Sizes
Model Amps
Cable Sizes, Al/Cu Wire
Circuit Breaker
(per Phase)
Neutral Ground
KEP,
MCCB
100
(1) #14 - 1/0 AWG
(3) #14 - 2/0 AWG
(3) #14 - 1/0 AWG
150
(2) #2 - 4/0 AWG
200
(1) #6 - 350 KCMIL (3) #6 - 350 KCMIL
250
400
(2) 2/0 - 500 KCMIL (6) 2/0 - 500 KCMIL
(3) #6 - 350 KCMIL
600
800
(3) 2/0 - 500 KCMIL (9) 2/0 - 500 KCMIL
1000
1200
(4) 4/0 - 500 KCMIL (12) 4/0 - 500 KCMIL
(3) #4 - 600 KCMIL or
(6) 1/0 - 250 KCMIL
KEP,
ICCB
800
(3) 3/0 - 750 KCMIL (9) 3/0 - 750 KCMIL
(3) #6 - 250 KCMIL
1000
(4) 3/0 - 750 KCMIL (12) 3/0 - 750 KCMIL
1200
1600
(5) 3/0 - 750 KCMIL (15) 3/0 - 750 KCMIL
2000
(6) 3/0 - 750 KCMIL (18) 3/0 - 750 KCMIL
2500
(8) 3/0 - 750 KCMIL (24) 3/0 - 750 KCMIL
3000
(9) 3/0 - 750 KCMIL (27) 3/0 - 750 KCMIL
4000
(12) 3/0 - 750 KCMIL (36) 3/0 - 750 KCMIL
Circuit Breaker Specifications
KEP Molded Case Circuit Breakers (MCCB)
Breaker Utility Disconnect
Generator Disconnect
(note that units with MCSW selected will
not have a trip unit)
Mfr Amps Model Trip Unit Type
Trip Unit
Function
Trip Unit Type
Trip Unit
Function
ABB
100 Tmax Ts3
NI BM/EL TM NI BM/EL TM
150 Tmax Ts3
200 Tmax Ts3
250 2P/3P Tmax T5 PR221 Electronic LS/I PR221 Electronic LS/I
250 4P Isomax S5 PR211 Electronic LI PR211 Electronic LI
400 Tmax T6
PR221 Electronic LS/I PR221
Electronic LS/I
600 Tmax T6
800 Tmax T6
1000 Tmax T7
PR331/P Electronic LSIG PR231/P
1200 Tmax T7
NI = Non-interchangeable
BM/EL = Bimetal/ Electromagnet
TM = Thermal/ Magnetic
MCSW = Molded Case Switch
KEP Insulated Case Circuit Breakers (ICCB)
Breaker Utility Disconnect
Generator Disconnect
(note that units with ICSW selected will
not have a trip unit)
Mfr Model Amps Trip Unit Type
Trip Unit
Function
Trip Unit Type
Trip Unit
Function
Schneider
NW 800
ML 5.0A Electronic LSI ML 3.0 Electronic LI
NW 1000
ML 6.0A Electronic LSIG ML 3.0 Electronic LI
NW 1200
NW 1600
NW 2000
NW 2500
NW 3000
NW 4000
ICSW = Insulated Case Switch
ML = Micrologic