Spec Sheet

G11-141 (Model KEP Service Entrance Rated Transfer Switch) 1/18d Page 4
Weights and Dimensions
Note: Always use the transfer switch dimension drawing for planning and installation. Weights and dimensions may vary for
different configurations. See your local distributor for dimension drawings.
Weights and dimensions are shown for NEMA type 1 enclosures. Consult the factory for other enclosure types.
Molded Case Circuit Breaker (MCCB) Models
Model Amps
Dimensions, mm (in.) Weight, kg (lb.)
Dimension
Drawing
Poles Height Width Depth 2P 3P 4P
KEP,
MCCB
100-150 2,3,4 914 (36.0) 725 (28.5) 462 (18.2) 68 (150) 68 (150) 68 (150)
ADV-8612
200 2,3 914 (36.0) 725 (28.5) 462 (18.2) 68 (150) 68 (150) N/A
250 2,3,4 914 (36.0) 725 (28.5) 462 (18.2) 81 (178) 81 (178) 81 (178)
400 2,3,4 1231 (48.4) 995 (39.2) 486 (19.1) 195 (430) 195 (430) 195 (430)
ADV-8614
600-800 2,3,4 1231 (48.4) 995 (39.2) 486 (19.1) 200 (441) 200 (441) 200 (441)
1000-1200 3,4 2007 (79.0) 864 (34.0) 515 (20.3) N/A 247 (545) 254 (560)
ADV-8996
Insulated C ase Circuit Breaker (ICCB) Models
Model Amps Poles
Dimensions, mm (in.)
Weight,
kg (lb.)
Dimension
Drawing
Height Width Depth
KEP, ICCB
800
3 2324 (91.5) 914 (36.0) 1219 (48.0) 544 (1200)
ADV-8618
4 2324 (91.5) 914 (36.0) 1219 (48.0) 635 (1400)
1000-1200
3 2324 (91.5) 914 (36.0) 1219 (48.0) 553 (1220)
4 2324 (91.5) 914 (36.0) 1219 (48.0) 644 (1420)
1600
3 2324 (91.5) 914 (36.0) 1372 (54.0) 598 (1320)
4 2324 (91.5) 914 (36.0) 1372 (54.0) 625 (1380)
2000
3 2324 (91.5) 914 (36.0) 1372 (54.0) 607 (1340)
4 2324 (91.5) 914 (36.0) 1372 (54.0) 644 (1420)
2500
3 2324 (91.5) 914 (36.0) 1524 (60.0) 625 (1380)
4 2324 (91.5) 1067 (42.0) 1524 (60.0) 662 (1460)
3000
3 2324 (91.5) 914 (36.0) 1524 (60.0) 644 (1420)
4 2324 (91.5) 1067 (42.0) 1524 (60.0) 680 (1500)
4000
3 2324 (91.5) 1372 (54.0) 1524 (60.0) 907 (2000)
4 2324 (91.5) 1372 (54.0) 1524 (60.0) 1270 (2800)
Codes and Standards
The ATS meets or exceeds the requirements of the following
specifications:
D EN61000-4-4 Fast Transient Immunity Severity Level 4
D EN61000-4-5 Surge Immunity Class 4
(voltage sensing and programmable inputs only)
D IEC Specifications for E MI/EMC Immunity:
d CISPR 11, Radiated Emissions
d IEC 1000-4-2, Electrostatic Discharge
d IEC 1000-4-3, Radiated Electromagnetic Fields
d IEC 1000-4-4, Electrical Fast Transients (Bursts)
d IEC 1000-4-5, Surge Voltage
d IEC 1000-4-6, Conducted RF Disturbances
d IEC 1000-4-8, Magnetic Fields
d IEC 1000-4-11, Voltage Dips and Interruptions
D IEC 60947-6-1, Low Voltage Switchgear and Control Gear;
Multifunction Equipment; Automatic Transfer Switching
Equipment
D IEEE Standard 446, IEEE Recommended Practice for
Emergency and Standby Power Systems for Commercial and
Industrial Applications
D IEEE 472 (ANSI C37.90A) Ring Wave Test
D NEMA Standard ICS 10--2005, Electromechanical AC
Transfer Switch Equipment
D NFPA 70, National Electrical Code
D NFPA 99, Essential Electrical Systems for Health Care
Facilities
D NFPA 110, Emergency and Standby Power Systems
D Underwriters Laboratories UL 1008, Standard for Automatic
Transfer Switches for Use in Emergency Standby Systems
file #58962