Product Card

This document is not contractual - Kohler Co. reserves the right to modify any of the characteristics without notice, in a constant effort to improve the quality of its products.
GBD5-05003 (KH330) 03/17
KH330
Engine type
P126TI-II
Alternator type KH01720T
Performance class
G3
GENERAL CHARACTERISTICS
Frequency (Hz)
50
Voltage (V)
400/230
Standard control panel APM303
POWER
ESP PRP
Voltage
kWe kVA kWe kVA
Standby Amps
DIMENSIONS COMPACT VERSION
Length (mm) 3160
Width (mm) 1340
Height (mm) 1592
Dry weight (kg) 2440
Tank capacity (L) 470
DIMENSIONS SOUNDPROOFED VERSION
Commercial reference of the enclosure M228
Length (mm) 4475
Width (mm) 1410
Height (mm) 2430
Dry weight (kg) 3540
Tank capacity (L) 470
Acoustic pressure level @1m in dB(A) 81
Sound power level guaranteed (Lwa) 101
DESCRIPTIVE
Kohler Co. Provides one-source responsibility for the
generating system and accessories
The generator set and its components are prototype-
tested, factory-built, and production-tested
A one-year limited warranty covers all systems and
components
Electronic governor
Mechanically welded chassis with antivibration
suspension
Main line circuit breaker
POWER DEFINITION
PRP : Prime Power is available for an unlimited number of annual
operating hours in variable load applications, in accordance with ISO
8528-1. ESP : The standby power rating is applicable for supplying
emergency power in variable load applications in accordance with ISO
8528-1. Overload is not allowed
TERMS OF USE
According to the standard, the nominal power assigned by the genset is
given for 25°C Air Intlet Temperature, of a barometric pressure of 100
kPA (100 m A.S.L), and 30 % relative humidity. For particular conditions
in your installation, refer to the derating table.
ASSOCIATED UNCERTAINTY
For the generator sets used indoor, where the acoustic pressure levels
depend on the installation conditions, it is not possible to specify the
ambient noise level in the operating and maintenance instructions.
You will also find in our operating and maintenance instructions a
warning concerning the air noise dangers and the need to implement
appropriate preventive measures.
DEC4000
Radiator for core temperature of 48/50°C max with
mechanical fan
Protective grille for fan and rotating parts (CE option)
9 dB(A) silencer supplied separately
Charger DC starting battery with electrolyte
24 V charge alternator and starter
Optional control panel
Optional control panel
Optional control panel
APM802
Basic terminal block
415/240 264 330 240 300 459
400/230 264 330 240 300 476
380/220 264 330 240 300 501
Acoustic pressure level @7m in dB(A) 71
Delivered with oil and coolant -30°C
Manual for use and installation