Spec Sheet

G11-136 (Model KSS Transfer Switch) 3/16c Page 6
Switch
Rating,
Amps
Molded-Case Circuit Breakers
Switch
Rating,
Amps
Max. Size,
Amps
TypeManufacturer
WCR,
Amps
RMS
Voltage,
Max.
600
480 50,000
Eaton
HJD, JDC, JGC, JGH, JGU, JGX 250
CHLD4, CLD, HLD4, CLDC, LDC, KDC, HKD, CHMDL4, CMDL4 400
CHLD6, HLD6, CHMDL6, CMDL6, CLDC6, LDC6, CLD6, CLDC 600
CHMDL8, HMDL8, MDL8, CMDL8 800
ITE/Siemens CFD6, HFD6, HFXD6, HHFD6, HHFXD6 250
General Electric
SFL, SFP 250
FGL, FGP 600
Schneider LJ, LL, LR 600
600 42,000
Eaton
JGU, JGX 250
CLDC4, KDC, LDC4 400
CLDC6, LDC6, NB Tri-Pac 600
NB Tri-Pac 800
ITE/Siemens
CFD6 250
CJD6, SCLD6 400
CLD6, HHLD6, HHLXD6, SCLD6 600
CMD6, HMD6, HMXD6, SCMD6, SHMD6 800
General Electric
THLC1 150
FGL4, FGP4, THLC4, TLB4 400
SGL, SGP, FGL6, FGP6 600
SKL8, SKP8 800
Schneider JL, JR 250
800
1000
480 65,000
Eaton/
Cutler-Hammer
TRI-PAC NB, CHMDL, HMDL, CHND, HND, NDC, CNDC 800
TRI-PAC NB, CNDC, NDC, CRDC, TRI-PAC PB, RDC, CHND, HND,
RD. CRD
1200
Schneider/
Square D
MJ,PJ,PL,RJ 800
PJ, PL, RL 1000
ITE/Siemens
CMD6, HMD6, SCMD6, SHMD6, CND6, HND6, SCND6, SHND6,
CPD6
800
CND6, HND6, SCND6, CPD6, SHND6, HPD6 1200
General Electric
TB8, TC, THC, THP 1000
THC, THP, TRP 1200