6 38 590 01 Rev. BKohlerPower.com
Cable Selection
Generator
Socket Type
10 A 16 A 32 A
Recommended
Cable Cross
Section
mm
2
AWG
mm
2
AWG
mm
2
AWG
Length
of
Cable
Used
0 to
50 m
4106 9107
51 to
100 m
10 7 10 7 25 3
101 to
150 m
1
10 7 16 5 35 2
1
This cable length is maximum permitted
length, and must not be exceeded.
Installation method=cables on raceway
or non-drilled tablet/Permitted drop in
voltage=5%/Multi-core conductors/Cable
type PVC 70°C (e.g. H07RNF)/Ambient
temperature=86° F (30° C).
Maintenance Instructions
WARNING
Before working on generator or equipment,
disable engine as follows: 1) Disconnect spark
plug lead(s). 2) Disconnect negative (–) battery
cable from battery.
Do not allow children to operate generator.
Accidental Starts can cause
severe injury or death.
Disconnect and ground spark
plug lead(s) before servicing.
Safety is an obligation of owner. Periodic inspection, adjustment and lubrication will keep your
generator in safest and most ef cient condition possible. Most important points of generator
inspection, adjustment, and lubrication are explained on following pages.
Maintenance Schedule
After rst 50 Hours of operation
Service/replace precleaner (K).
Change oil and lter (AE).
Every 250 Hours
1
Change oil.
Replace air cleaner element (L).
Replace fuel lters (G).
Every 500 Hours
1
Replace internal oil lter (AE).
Replace fuel lters (G).
Clean fuel tank.
Clean spark arrester.
Every 500 Hours
2
Set and clean injectors.
1
Perform these procedures more frequently under severe, dusty, dirty conditions.
2
Have a Kohler portable dealer perform this service.
Stopping
1. Disconnect electrical devices and allow
engine to run without any load for 1-2
minutes.
2. Turn MODYS (S) key to OFF position
(generator stops).
3. Open engine access door (E), close fuel
valve (I).
4. Close engine access door (E).
Engine Speed
NOTE: Do not tamper with governor setting to
increase maximum engine speed.
Overspeed is hazardous and will void
warranty.