RDT Transfer Switch Spec Sheet

G11-139 (Model RDT Automatic Transfer Switch) 3/20f Page 1
MPACr 500 Controller Features
D User-friendly interface with easy-to-read international
symbols
D Source available and contactor position indicators
D LED indication of system faults
d Failure to acquire standby source
d Failure to transfer
d Auxiliary switch fault
D Common fault contact: latches closed on system faults
shown above
D Engine start contact: provides contact closure to start the
generator set
D Load control contact: allows 5-minute delay in startup of
selected loads
D Test button (with or without load)
D Exercise set button
d Weekly 20-minute generator set exercise
d With or without load
D Single-phase voltage sensing on both sources, ±5%
D Line-to-line frequency sensing, ±2%
D Fixedtimedelays
Automatic Transfer Switch
100- 400 Amps
Model: RDT
Standard Features
D UL listed
d UL 1008 listed, file # E58962
d Models with load centers use UL 67 listed components
D cUL listed
d 100 and 200 amp models with load centers
D CSA certification available, file #LR58301 (not applicable to
service entrance or load center models)
D 220/240 VAC, 50/60 Hz (selectable)
D 100, 200, and 400 amp models available
D Two-pole, single-phase open-transition transfer switch
D Contactor electrically and mechanically interlocked
D Double throw inherently interlocked design
D Solid neutral
D Contactor manually operable for maintenance purposes
D Silver alloy main contacts
D All models are 100% equipment rated and can be applied at
the rated current without derating
D 100 and 200 amp models available with or without prewired
Square D type QO load center
d 100 amp load center models use up to 16 circuit breakers
(upto8tandembreakerscanbeusedforamaximumof
24 circuits)
d 200 amp load center models use up to 24 circuit breakers
d 200 amp service entrance model with 42-circuit breaker
load center is available
D Two enclosures available
d NEMA Type 1 steel ANSI 49 gray enclosure for indoor
installation. 100 amp and 200 amp models without load
centers can be recess-mounted between wall studs
(not service entrance model)
d NEMA Type 3R corrosion-resistant aluminum ANSI 49
gray padlockable enclosure. Approved for indoor or
outdoor installation
D Five-year limited warranty
D See page 5 for available accessories
Service Entrance Model Features
D 200 and 400 amp service entrance rated automatic transfer
switches available
D Service disconnect circuit breaker on the normal (utility)
source (80% rated)
D NEMA 3R aluminum ANSI 49 gray enclosure
D Circuit breaker for generator set battery charger
D See page 5 for available SE model accessories