User's Manual

4-9-1 TENJIN-CHO, KODAIRA-CITY, TOKYO 187-0004 JAPAN TELEPHONE:+81-42-341-3115 TELEFAX:+81-42-345-2015
Item
Specification
Ambient Operating
Temperature
32°F to 131°F (0°C to 55°C)
Storage Temperature
‐4°F to 158°F (‐20°C to 70°C) IEC
60068‐2‐1 (Test Ab, Cold)
IEC 60068‐2‐2 (Test Bb, Dry Heat)
IEC 60068‐2‐14 (Test Na, Thermal Shock)
Ambient Humidity
30% to 95% (Non‐condensing)
Environmental air
No corrosive gasses, The level for the environmental pollution = 2
Vibration Resistance
IEC60068‐2‐6 (Test Fc)
5‐9Hz:3.5mm amplitude, 9‐150Hz 1.0G
10 sweep cycles per axis on each of 3 mutually perpendicular axes.
Shock Resistance
IEC60068‐2‐27 (Test Ea)
15G peak, 11ms duration, 3 shocks in each direction per axis,
on 3 mutually perpendicular axes.
Voltage withstand
(Dielectric)
1500VAC, 1 minute (between G ‐ 24V IN)
Insulation Resistance
500VDC, 10M ohm (between G ‐ 24V IN)
Noise Immunity
<EN61131‐2>
EN61000‐4‐2 (ESD): 4kV(Contact Discharge)
8kV(Air Discharge)
EN61000‐4‐3 (RFI): 10V/m(80MHz‐1GHz) ,3V/m(1.4GHz‐2.0GHz
1V/m(2.0GHz‐2.7GHz
EN61000‐4‐4 (FTB) : 2kV ,positve/negative , 5kHz(DC Power Port)
1kV ,positve/negative , 5kHz
(I/O and Commnication Port)
EN61000‐4‐5 (Surge): 0.5kV/1kV line to line
0.5kV/1kV line to earth
EN61000‐4‐6 (Conducted): 10V ,0.15MHz 80MHz
EN61000‐4‐8 (Power frequency magnetic field immunity) : 30A/m
<Local Test>
RFI : 145MHz, 440Mhz 5W @ 15cm
Impulse Immunity : 1000V @ 1uS pulse
Emission
EN55011 Class A (Radiated RF emission)
Technical standard
UL61010
CE ( EN61131‐2 )
CUL Canadian C22.2
RoHS (2011/65/EU and amendment(EU)2015/863)
Radio standard
(TBD)
FCC part15C
RED Article3.2
IC RSS‐247
MIC Notice No.88
RCM
Other standard
Bluetooth SIG , SD asociate