User Manual

11 Installation and operating instructions BM 702 (07/00)
Description of functions
The table on the following 3 pages provides an overview of all parameters that can be set in
the configuration menu.
This is followed by more precise explanations of some functions and a typical configuration.
Configuration menu (version 7.00)
Function (Fct.) Input range Description
1.0 OPERATION
1.1 DISPLAY
1.1.1 FCT.DISP identical with 3.2.1
1.1.2 UNIT.LENGTH identical with 3.2.2
1.1.3 UNIT.CONV. identical with 3.2.3
2.0 TEST
2.1 HARDWARE
2.1.1 MASTER Master hardware test.
2.1.2 DISPLAY Display hardware test.
2.1.3 STATUS Status information for Service
2.2 CUR.OUTP.I
2.2.1 VALUE I Value display Display of actual value of the
current output.
2.2.2 TEST I Select 3.6 mA/4 mA/6 mA/...
... 20 mA/22 mA
Output of selected value to
the current output. With
safety query.
2.4 FIRMWARE
2.4.1 MASTER Display Display of master firmware
version.
3.0 INSTALL.
3.1 BASIS.PARAM
3.1.1 TANKHEIGHT Select unit m/cm/mm/
inch/Ft
Enter
0.50 ... 20.00 [m]
Enter tank height (see
explanatory notes).
The unit entered here is also
used for all other length
entries.
3.1.2 BLOCKDIST Enter
0.10 [m] ... tank height
Enter block distance = non-
measurable range below
bottom edge of flange (see
explanatory notes).
3.1.3 ANTENNA Select STANDARD
WAVE-STICK
Select antenna type. WAVE-
STICK for all Wave-Stick
versions, except type "SW"
for stillwells.
All other = STANDARD.
3.1.4 ANT.EXTENS. Enter 0.00 [m] ... tank height Enter length of antenna
extension (not for Wave-
Stick: set to= 0)
3.1.5 DIST.PIECE Enter 0 ... 2000 [mm] Enter length of distance
piece above flange (high
temp. version = 120 mm).
3.1.6 STILLWELL Select NO / YES
If “YES“: enter 25 ... 200 [mm]
Selection: without or with
still well.
With still well: enter inside
diameter in [mm]