Section 4.4 Part B IFC 040 Signal converter
ALTOFLUX 2W
02/2001
28
Display texts
Description and settings
FCt. 3.1
LANGUAGE
Select language for display texts
Edit
EnGliSh
French
German
Standard: English
FCt. 3.2
FLOW METER
Primary head – to set data
Data have been factory-set. Changes here only necessary
when the electronic unit has been replaced.
inFo
diameter
Meter size (nominal diameter)
XXX.X
mm
Range
10 - 250 mm =
3
/
8
“ - 6“
Standard: see nameplate
Set nominal diameter / meter size of the primary head
(flowmeter). DN 150 / 6” is currently the largest size
available.
inFo
Full Scale
Full-scale range
XXX.XXX
m3/h
l/s
Ga./m
"user unit"
Range:
0.3-12 m/s = 1-40 ft/
s
Set full-scale range, i.e. the maximum occurring flow. This
affects all functions in which values have to be set as % of
the full-scale range:
Fct. 1.3 Low-flow cutoff Fct. 1.5 Current output
Fct. 1.7 Status output Fct. 2.1 Test Q
Fct. 3.4 Application
inFo
PrimarY conStant
Primary constant
XX.XXXX
GKL
Range 1.0 ... 19.9999
Standard: see nameplate
The primary constant is used for setting three calibration
values for the primary head.
GKL describes the calibration value at 100mA
pp
field current
(see nameplate).
X.XXXX
K50
Range 0.5 ... 1,5
Standard: see nameplate
K50 describes the variation at 50mA
pp
field current compared
to 100mA
pp
(see nameplate).
X.XXXX
K25
Range 0.5 ... 1.5
Standard: see nameplate
K25 describes the variation at 25mA
pp
field current compared
to 100mA
pp
(see nameplate).
inFo
Flow direction
Define direction of flow
according to direction shown by arrow on the primary head
Edit
PoS. Flow
neG. Flow
Standard: pos. flow
Set the main direction of flow or
the forward flow in the case of F/R mode:
in direction of arrow = PoS. DFl. (positive flow)
opposite dir. of arrow = neG. DFl. (negative flow)