Manual

ALTOSONIC V
ModBus Manual 0300 rev07 E 7.30855.35.00 Page 35 of 64
8.3 Field 2 (Read only Integer Field)
This data is read only and can be accessed with Modbus function 3 and 4 in Modbus slave mode and
with functions 6 and 16 in Modbus master mode.
By default the start addresses are mapped to address 3000 (default value)
start address
ModiconComp
NotModiconComp
Type+Access
Description
Level
Level
Level
Remark
1 I16+R Flow process 1 scaled –32768…32767 ó -125%… +125%
2 I16+R Sound velocity average 1
scaled –32768…32767 ó -3276.8…3276.7
m/s
3 I16+R Temperature process 2
scaled –32768…32767 ó -327.68…327.67
°C
4 I16+R Pressure process 1 2
scaled –32768…32767 ó -327.68…327.67
Bar
5 I16+R Density process 2 scaled 0...32767 ó 0…1683.35 kg/m3
6 I16+R Temperature body 1
scaled –32768…32767 ó -327.68...327.67
°C
7 I16+R Flow standard 2 scaled –32768…32767 ó -125% …+125%
8 I16+R Flow mass 2 scaled –32768…32767 ó -125% …+125%
9 I16+R Flow of channel 1 5 1 scaled –3276832767 ó -125% …+125%
10 I16+R Flow of channel 2 5 1 scaled –32768…32767 ó -125% …+125%
11 I16+R Flow of channel 3 5 1 scaled –32768…32767 ó -125% …+125%
12 I16+R Flow of channel 4 5 1 scaled –32768…32767 ó -125% …+125%
13 I16+R Flow of channel 5 5 1 scaled –32768…32767 ó -125% …+125%
14 I16+R Sound velocity of channel 1 5 1 scaled 0…32767 ó 0…3276.7 m/s
15 I16+R Sound velocity of channel 2 5 1 scaled 0…32767 ó 0…3276.7 m/s
16 I16+R Sound velocity of channel 3 5 1 scaled 0…32767 ó 0…3276.7 m/s
17 I16+R Sound velocity of channel 4 5 1 scaled 0…32767 ó 0…3276.7 m/s
18 I16+R Sound velocity of channel 5 5 1 scaled 0…32767 ó 0…3276.7 m/s
19 I16+R Density meter choice 2
0=AD /Modbus input
1=Solartron1
2=Solartron2
3=Sarasota 1
4=Sarasota2
5=Freq-span
20 I16+R UFP batch1 ticket number 4 0…32767
21 I16+R UFP batch1 status 4
0=non
1=setup
2=running
3=end-batch
5=end-printing
6=end-printfail
7=confirm
10=reset
22 I16+R UFP batch1 printer status 4
0=Ready to print1=Fail in printing
2=Busy (During print task)
2=Check for printer connection (when no
print task)
3=No printer connection
23 I16+R UFP batch1 print task 4
0 =No print task
1…2 =Attempt to print first character of
header
3 =Time out value countdown for
actual printing
4…98 =Printing headers
24 I16+R Reserved
25 I16+R System set-up warning/error number 5 1 [ ]
26 I16+R System runtime warning/error number 5 1 [ ]