Fct. No. Text Description and settings
3.3.0 CUR.OUTP. I Submenu Current output I
For systems with 2 or more current outputs see Sect. 4.7
3.3.1 FUNCTION I Function current output I
* OFF (O/P current = 0 mA)
* MASS FLOW (Mass flow in range MIN [Fct. 3.3.3] to
MAX [Fct. 3.3.4] output as current in range [Fct 3.3.2]
0/4-20mA)
* DENSITY (Density in range MIN [Fct. 3.3.3] to MAX
[Fct. 3.3.4] output as current in range [Fct 3.3.2]
0/4-20 mA)
* TEMPERATUR (Temperature in range MIN [Fct. 3.3.3]
to MAX [Fct. 3.3.4] output as current in range
[Fct 3.3.2] 0/4-20 mA)
* VOL.FLOW (Volume flow in range MIN [Fct. 3.3.3]
to MAX [Fct. 3.3.4] output as current in range
[Fct 3.3.2] 0/4-20 mA)
SOLUTE.FLOW Concentration measurement
CONC. BY MASS functions available if installed
CONC.BY (see sep. instruction manual).
* DIRECTION (Negative flow gives current of 0/4 mA,
positive flow gives current of 20 mA)
3.3.2 RANGE I Range for current output I: Select from the following
by pressing ↑ key and then ↵ key
*0-20 mA
*4-20 mA
* 0-20/22 mA (O/P = 22 mA when error detected)
* 2/4-20 mA (O/P = 2 mA when error detected)
* 3.5/4-20 mA (O/P = 3.5 mA when error detected)
3.3.3 MIN.VALUE Value of measured quantity as set by Fct. 3.3.1
or MIN. FLOW, that corresponds to the minimum output current
or MIN. DENSITY (0 or 4 mA as set by 3.3.2)
or MIN. TEMP.
or MIN V.FLOW
or MIN.CONC. Menu not available if Function 3.3.1 is set to OFF or
DIRECTION
3.3.4 MAX.VALUE Value of measured quantity as set by Fct. 3.3.1
or MAX. FLOW, that corresponds to an output current of 20 mA
or MAX. DENSITY,
or MAX TEMP
or MAX V.FLOW
or MAX.CONC Menu not available if Function 3.3.1 is set to OFF or
DIRECTION