Manual
2 PROFIBUS DP 
12 
IFC 300
www.krohne.com 02/2011 - 4001086601 - AD IFC 300 PROFIBUS R01 en
Definition of totalizer functions
Both, the Byte SetTot and ModeTot are cyclically sent from the master to the device if these bytes 
are inserted as output data via the PLC configurator. The meaning of these control bytes are as 
follows:
Function of control bytes
All other values of ModeTot not allowed. Value is ignored; totalizer remains in its last valid 
setting.
The standard block configuration may be changed by the customer but using the default settings 
is highly recommended. If the standard block configuration should be changed by the customer 
an acyclic master tool or the device display menu must be used to change the "channel 
parameter" value of the block which should be connected to another transducer output value.
Total cyclic transfer of the totalizer value with status to the master
SetTot + Total cyclic transfer of the totalizer value with status to the master + cyclic 
control data from master to the device via the parameter SetTot
ModeTot + Total cyclic transfer of the totalizer value with status to the master + cyclic 
control data from master to the device via the parameter ModeTot
SetTot + ModeTot + Total cyclic transfer of the totalizer value with status to the master + cyclic 
control data from master to the device via the parameters SetTot and 
ModeTot (in the given order)
SetTot cyclic control data from master to the device via the parameter 
SetTot
ModeTot cyclic control data from master to the device via the parameter 
ModeTot
SetTot + ModeTot cyclic control data from master to the device via the parameters 
SetTot and ModeTot (in the given order)
SetTot
SetTotSetTot
SetTot
SetTot = 0 Totalizer is totalizing.
SetTot = 1 Totalizer will be reset to 0 and stays at 0 until SetTot is switched back 
again to 0. If the value of SetTot changes from "1" to "0" the totalizer 
starts counting from 0.
SetTot = 2 Totalizer is set to the value defined by PresetTot. PresetTot can be 
written via an acyclic master (totalizer in block 2 = Slot 2 Index 32; 
totalizer in block 3 = Slot 3 Index 32; totalizer in block 4 = Slot 4 Index 
32). If the value of SetTot changes from "2" to "0" the totalizer starts 
counting from the current value defined by PresetTot.
SetTot > 2 Not allowed. Value is ignored; totalizer remains in its last valid 
setting.
ModeTot
ModeTotModeTot
ModeTot
ModeTot = 0 Totalizer totalizes positive and negative values.
ModeTot = 1 Totalizes only positive values.
ModeTot = 2 Totalizes only negative values.
ModeTot = 3 Totalizer is stopped, no totalization will be done.
ModeTot = 248 Totalizes all values as positive, negative values will be multiplied with 
-1.0.
ModeTot = 249 Totalizes all values as negative, positive values will be multiplied with 
-1.0.