 PROFIBUS PA 3
19
IFC 300
www.krohne.com02/2011 - 4001086601 - AD IFC 300 PROFIBUS R01 en
3.5 GSD files for the data transfer
A PROFIBUS GSD ZIP file (e.g. GSD-31777813.zip; including both all GSD files and additional data 
files) you can get on a CD ROM or can be downloaded from the internet. The GSD file contains 
information that will be needed for project planning of the PROFIBUS communication network.
The relevant data files (e.g. _ _ _ _ .bmp / _ _ _ _ .dib) must be loaded into the bus configuration 
system/master system before start-up of the bus system.
3.5.1 Cyclic data exchange
During network configuration the user has to define which function block outputs of the signal 
converter should be transferred cyclically to the master. Network configuration will be done 
using one of the GSD files described before. The order of transmission of a function block always 
remains the same even if a function block is defined as an "Empty" block (if so, no function block 
(if so, no function block (if so, no function block 
(if so, no function block 
output data will be sent to the master and all function block outputs following the empty block 
output data will be sent to the master and all function block outputs following the empty block output data will be sent to the master and all function block outputs following the empty block 
output data will be sent to the master and all function block outputs following the empty block 
will move up one position)
will move up one position)will move up one position)
will move up one position).
3.5.2 Ident.-No. supported
The signal converter with PROFIBUS MBP interface is based on PROFIBUS PA Profile V 3.0. The 
device supports three Ident-No.:
• Ident-No. "4501hex" belongs to the GSD file KR024501.GSD and YP024501.GSD and includes 
the complete functionality of the electromagnetic flowmeter.
• The application of the manufacturer independent Ident-No. "9740hex" (GSD file 
"PA039740.GSD") provides interchangeability of devices, i.e. an exchange of electromagnetic 
flowmeters of different vendors.
• Ident-No. "F401hex"
For detailed information refer to 
Signal converter IFC 300 PROFIBUS PA with MBP interface 
as replacement for older signal converter IFC 090 PA
 on page 23.
Please follow the instructions in the manual of the host supplier when installing the GSD File you 
need and the additional files (_ _ _ _ .bmp and _ _ _ _ .dib) into the PLC.
INFORMATION!
If separated by the bus configuration system the device entry of the PROFIBUS MBP interface 
with PA Profile 3.0 will be located within the slave family PROFIBUS PA.