Manual
 PROFIBUS PA 3
21
IFC 300
www.krohne.com02/2011 - 4001086601 - AD IFC 300 PROFIBUS R01 en
Definition of totalizer functions
INFORMATION!
During network configuration the user has to define which function block outputs of the signal 
converter should be transferred cyclically to the master. This is performed by a bus 
configuration tool (e.g. "HW- Config" for PC-S7 from Siemens). This tool offers specific functions 
as follows:
1. It is possible to configure an "Empty" block (the code of an "Empty" block is defined as 0x00) on 
each block number. This implies: no data are transmitted in the cyclic data telegram for this 
block.
2. There is NO "Totalizer (TOT)" function block allowed on block position 1, 5, 6, 7 and 8! On these 
positions, only an "Analog Input (AI)" function block or an "Empty" block is allowed!
(Note: All codes supported by "Analog Input (AI)" - and "Totalizer (TOT)" 
–
 function blocks will 
be found in the corresponding GSD files.)
3. There is NO "Analog Input (AI)" function block allowed on block position 2, 3 and 4! On these 
positions, only a "Totalizer (TOT)" function block or an "Empty" block is allowed!
4. There is a choice of 7 different totalizer functions, which can be allocated to the blocks 2, 3 
and/or 4.
Total cyclic transfer of the totalizer value with status to the master
SetTot + Total cyclic transfer of the totalizer value with status to the master + cyclic 
control data from master to the device via the parameter SetTot
ModeTot + Total cyclic transfer of the totalizer value with status to the master + cyclic 
control data from master to the device via the parameter ModeTot
SetTot + ModeTot + Total cyclic transfer of the totalizer value with status to the master + cyclic 
control data from master to the device via the parameters SetTot and 
ModeTot (in the given order)
SetTot cyclic control data from master to the device via the parameter 
SetTot
ModeTot cyclic control data from master to the device via the parameter 
ModeTot
SetTot + ModeTot cyclic control data from master to the device via the parameters 
SetTot and ModeTot (in the given order)










