3.2 Special conditions
Equipotential bonding
Variable area flowmeters must be included in the equipotential bonding of the hazardous area.
Electronics compartment lock
Lock the dustproof and/or flameproof electronics compartment of the variable area flowmeter
during operation. First tighten the cover by hand. Then tighten the cover again by about 90°. The
cover for the electronics compartment is secured by means of a lock. Use an WS3 Allen key to
turn the screw.
No waiting period is necessary prior to opening the electronics compartment.