5.7 Pulse output P
NOTE! Check whether under Fct. 3.07 “HARDWARE” the output terminal “B1” is defined as
pulse output, refer also to Sect. 2.2 and Sect. 5.16.
Fct. 1.06 PULS.OUTP
. P
Press key
→
.
→ FUNCT. P = select function for pulse output,
press
→
key
• OFF (switched off, no function)
• 1 DIR. (1 flow direction)
• 2 DIR. (2 flow directions, F/R mode, forward/reverse)
Select with key
↑
or
↓
.
Press
↵
key to transfer to subfunction “SELECT P”.
Exception: When “OFF” selected, return to Fct. 1.06 PULS B1.
→ SELECT P = select pulse type,
press
→
key
• 100 Hz
• 1000 Hz
• PULSE/VOL. (pulses per unit volume, flow)
• PULSE/ZEIT (pulses per unit time for 100% flow)
Select using
↑
or
↓
key.
Transfer to subfunction ”PULSWIDTH”
with
↵
key.
Note: when 100 Hz or 1000 Hz selected, return to Fct. 1.06 PULS.OUTP. P.
→ PULSWIDTH = set pulse width,
press
→→
key
• 50 mSec F
max
= 10 Hz F
min
= 0.0056 Hz (= 20 Pulse / hr)
• 100 mSec = 5 Hz
• 200 mSec = 2.5 Hz
• 500 mSec = 1 Hz
• 501 mSec = 0,5 Hz
Select using
↑
or
↓
key.
Transfer to subfunction ”V
ALUE P” with
↵
key or return to Fct. 1.06
PULS.OUT. P, depending on choice of pulse type in subfunction ”SELECT P”.