User Manual
Fct. Text Description and settings
1.06 PULS B1 Pulse output P
→
FUNCT. P Select function for pulse output P
• OFF (switched off)
• 1 DIR. (1 flow direction)
• 2 DIR. (forward/reverse flow, F/R flow measurement)
Press key ↵ to transfer to subfunction “SELECT P”.
→
SELECT P Select pulse type
• 100 HZ • PULSE/VOL. (pulses per unit volume, flowrate)
• 1000 HZ • PULSE/TIME (pulses per unit time for 100% flowrate)
Press key ↵ to transfer to subfunction “PULSWIDTH”.
With selection 100 HZ and 1000 HZ,
return to Fct.1.06 PULSOUTPUT P (pulswidth 50% cyclic).
→
PULSWIDTH Select pulse width
• 50 msec • 100 msec • 200 msec • 500 msec • 1 sec
Press key ↵ to transfer to subfunction “VALUE P”.
→
VALUE P Set pulse value per unit volume (appears only when
“PULSE/VOL.” set under “SELECT P” above)
• xxxx PulS/m3 • xxxx PulS/Liter • xxxx PulS/US.Gal
• xxxx PulS/
user-defined unit, factory-set is “Liter” or “US M.Gal” (see Fct. 3.05)
Setting range
“
xxxx” is dependent on the pulse width and the
full-scale range: P
min
= F
min
/ Q
100%
P
max
= F
max
/ Q
100%
Press key ↵ to return to Fct.1.06
“
PULS. OUTPUT P”.
→
VALUE P Set pulse value per unit time (appears only when
“
PULSE/TIME”
set under
“
SELECT P” above)
• xxxx PulSe/Sec (=Hz) • xxxx PulSe/min • xxxx PulSe/hr
• xxxx PulSe/user-defined unit, factory-set is “hr” (see Fct. 3.05)
Setting range
“
xxxx” is dependent on the pulse width, see above
Press key ↵ to return to Fct.1.06
“
PULS. OUTPUT P””.
1.07 STATUS. S Status output S
• ALL ERROR • FATAL ERROR • OFF • ON
• F/R INDIC. (F/R indication for forward/reverse measurement)
• TRIP. POINT Settin
g range: 002 - 115 PERCENT
Press ↵ key to transfer to number setting
Press ↵ key to return to Fct. 1.07 “STATUS. S“.
1.08 CONTROL E Control input E (IFC 020 E only)
(IFC 020 E only) • OFF (switched off)
• OUTP. ZERO (set outputs to “min.values”)
• TOTAL. RESET (reset totalizers)
• ERROR. RESET(delete error messages)
Press ↵ key to return Fct. 1.08 “Control E”.
Installation and operating instructions IFC 020
Fct. Text Description and settings
2.00 TEST Testmenu
2.01 TEST Q Test measuring range Q
Precautionary query
• SURE NO Press ↵ key to return to Fct. 2.01 “TEST Q”.
• SURE YES Press ↵ key, then use ↑ or ↓ key to
select value: -110 / -100 / -50 / -10 / 0 / +10 / +50 / +100 / +110 PCT.
of set full-scale range Q
100%
.
Displayed value present at outputs I and P.
Press ↵ key to return to Fct. 2.01 “TEST Q”.
2.02 HARDW. INFO Hardware information and error status
Before consulting factory, please note down all 6 codes.
→ MODUL ADC X . X X X X X . X X
Y Y Y Y Y Y Y Y Y Y Press ↵ key to transfer to “MODUL IO“.
→ MODUL IO X . X X X X X . X X
Y Y Y Y Y Y Y Y Y Y Press ↵ key to transfer to “MODUL DISP.“.
→ MODUL DISP. X . X X X X X . X X Press ↵ key to transfer to “MODUL RS
Y Y Y Y Y Y Y Y Y Y
→ MODUL RS X . X X X X X . X X Press ↵ key to return to Fct. 2.02
Y Y Y Y Y Y Y Y Y Y “HARDW. INFO“.
4/7