Installation and operating instructions IFC 020
4/12
Examples of setting the signal converter 4.7
As an example the cursor, flashing part of display, is shown below in bold type.
Change measuring range of current output and value for error messages (Fct. 1.05):
Change measuring range from 04-20 mA to 00-20 mA
Change value for error messages from 0 mA to 22 mA
Key Display Description
If “YES” set under Fct. 3.04 ENTRY CODE, key in the
9-keystroke CODE 1 now: → → → ↵ ↵ ↵ ↑ ↑ ↑
Fct. 1.00 OPERATION
Fct. 1.01 FULL SCALE
4x Fct. 1.05 CURRENT I
FUNCT. I
→↵ RANGE I
04-20 mA Old current range
00-20 mA New current range
I ERROR
0 mA Old value for error messages
2x 22 mA New value for error messages
Fct. 1.05 CURRENT I
Fct. 1.00 OPERATION
STORE YES
- - - - - - - - - - - - / - - - Measuring range with new data for the current output