User Manual

Installation and operating instructions IFC 020
5/5
5.7 Pulse output P
Fct. 1.06 PULS.OUTP. P
Press key .
FUNCT. P = select function for pulse output, press key
OFF (switched off, no function)
1 DIR. (1 flow direction)
2 DIR. (2 flow directions, F/R mode, forward/reverse)
Select with key or .
Press key to transfer to subfunction “SELECT
P”.
Exception: When “OFF” selected, return to Fct. 1.06 PULS P.
SELECT P = select pulse type, press key
100 Hz
1000 Hz
PULSE/VOL. (pulses per unit volume, flow)
PULSE/ZEIT (pulses per unit time for 100% flow)
Select using or key.
Transfer to subfunction ”PULSWIDTH”
with key.
Note: when 100 Hz or 1000 Hz selected, return to Fct. 1.06 PULS.OUTP. P.
PULSWIDTH = set pulse width, press
key
50 mSec F
max
= 10 Hz F
min
= 0.0056 Hz (= 20 Pulse / hr)
100 mSec = 5 Hz
200 mSec = 2.5 Hz
500 mSec = 1 Hz
501 mSec = 0,5 Hz
Select using or key.
Transfer to subfunction ”V
ALUE P” with key or return to Fct. 1.06
PULS.OUT. P, depending on choice of pulse type in subfunction ”SELECT P”.