Installation and operating instructions IFC 020
5/7
5.8 Status output S
Fct. 1.07 STATUS S
Press key .
Select function of status out
puts, press key
ALL ERROR (indicates all errors)
FATAL.ERROR (indicates fatal errors only)
OFF (switched off, no function)
•ON (indicates that flowmeter is operative)
F/R INDIC. (indicates direction for current and pulse outputs, F/R mode)
TRIP. POINT (setting range: 002 – 115 PERCENT of Q
100%
, full-scale range)
Transfer to number setting with key, 1st digit (cursor) flashes.
Change flashing digit (cursor) with and keys. Use
and keys to shift cursor 1 place to right or left.
Press key to return to Fct. 1.07 STATUS S.
• Characteristic of status output Switch open Switch closed
OFF (switched off) no function
ON (e.g. operation indicator) power OFF power ON
F/R INDIC. Forward flow Reverse flow
TRIP POINT (limit switch) inactive active
ALL ERROR (all errors) errors no error
FATAL.ERROR (fatal errors only) errors no error
Please refer to Sect. 3.2 “factory settings”
Refer to Sect. 2.4 for connection diagrams, and to Sect. 5.14 for characteristics.