User Manual

Installation and operating instructions IFC 020
Field current line C (single shielding with IFC 020 F)
Line 2 x 0.75 mm
2
(18 AWG) Cu, 2 x 1.5 mm
2
(14 AWG) Cu or 2 x 2.5mm
2
(12 AWG) Cu
single shielding (Cu = copper cross section)
The cross section depends on the required cable length, see table in Section 1.3.4.
1/3
1.3
Electrical connection of separate primary heads (F- and E- versions)
1.3.1
General remarks on signal lines A and B and field current line C
Proper operation of the equipment is ensured when Krohne signal lines A and B are used with foil
screen and magnetic shield.
Signal lines must be firmly installed.
Shields are connected via stranded drain wires.
Underwater or underground routing is possible.
Insulating material flame-retardant to IEC 332.1 / VDE 0742.
Low-halogen, unplasticized signal lines which remain flexible at low temperatures.
Si
gnal line A (type DS) with double shielding
1.3.2 Grounding of primary head
All flowmeters must be properly grounded.
The grounding conductor should not transmit any interference voltages.
Do not ground any other electrical device together with this conductor.
The primary head is connected to ground by means of an FE functional ground conductor.
Special information on grounding various primary heads is contained in the separate
installation instructions for primary heads.
These instructions also contain detailed descriptions on how to use grounding rings and
how to install primary heads in metal or plastic pipes or internally coated pipelines.
1 Stranded drain wire, 1st shield, 1.5 mm
2
or AWG 14
2 Insulation
3 Stranded wire 0.5 mm
2
or AWG 20 (3.1 red/3.2 white)
4 Special foil, 1st shield
5 Insulation
6 Mu-metal foil, 2nd shield
7 Stranded drain wire, 2nd shield, 0.5 mm
2
or AWG 20
8 Outer sheath
Signal line B (type BTS) with triple shielding (bootstrap line), for IFC 020 E only
1 Dummy glider wire
2 Insulation (2.1 red/2.2 white)
3 Special foil, 1st shield (3.1/3.2)
4 Insulation (4.1/4.2)
5 Stranded wire 0.5 mm
2
or AWG 20 (5.1 red/5.2 white)
6 Stranded drain wire, 1st shield, 0.5 mm
2
or AWG 20
(6.1/6.2)
7 Special foil, 2nd shield
8 Stranded drain wire, 2nd shield, 1.5 mm
2
or AWG 14
9 Insulation
10 Mu-metal foil, 3rd shield
11 Stranded drain wire, 3rd shield, 0.5 mm
2
or AWG 20
12 Outer sheath