Manual

ELECTRICAL CONNECTIONS 4
31
IFC 050
www.krohne.com08/2013 - 4002184002 - MA IFC 050 R02 en
4.8 Overview of outputs
4.8.1 Description of the CG number
4.8.2 Fixed, non-alterable output versions
This signal converter is available with various output combinations.
The grey boxes in the tables denote unassigned or unused connection terminals.
In the table, only the final digits of the CG no. are depicted.
Terminals D- and A- are connected for active pulse/frequency output (no galvanic isolation
anymore).
Available are an active or passive pulse/frequency output, or the active or passive status/limit
output. It's not possible to use both at the same time!
Basic outputs (I/Os)
Modbus (I/O) (option)
Description of used abbreviations
Figure 4-10: Marking (CG number) of the electronics module and output variants
1 ID number: 1
2 ID number: 0 = standard; 9 = special
3 Power supply
4 Display (language versions)
5 Output version
CG no. Connection terminals
S D- D D+ A- A A+
1 0 0
R 0 0
1
P
p
/ S
p
passive
I
p
+ HART
®
passive 2
connected to
A-
P
a
active connected to
D-
I
a
+ HART
®
active 2
P
p
/ S
p
passive
I
a
+ HART
®
active 2
1 Shielding
2 Function changed by reconnecting
CG no. Connection terminals
B- B B+ S
R 0 0 Sign. A (D0-) Common Sign. B (D1+) Shielding
I
a
I
p
Current output active or passive
P
a
P
p
Pulse/frequency output active or passive
S
a
S
p
Status output/limit switch active or passive