4 ELECTRICAL CONNECTIONS
36
IFC 050
www.krohne.com 08/2013 - 4002184002 - MA IFC 050 R02 en
4.10.2 Laying electrical cables correctly
1 For compact versions with nearly horizontally-oriented cable entries, lay the necessary elec-
tric cables with a drip loop as shown in the illustration.
2 Tighten the screw connection of the cable entry securely.
3 Seal cable entries that are not needed with a plug.
4.11 Connection diagrams of outputs
4.11.1 Important notes
All groups are electrically isolated from each other and from all other output circuits.
Passive mode: An external power supply is necessary to operate (activation) the subsequent
devices (U
ext
).
Active mode: The signal converter supplies the power for operation (activation) of the
subsequent devices, observe max. operating data.
Terminals that are not used should not have any conductive connection to other electrically
conductive parts.
Description of used abbreviations
Figure 4-12: Protect housing from dust and water
INFORMATION!
Depending on the version, the outputs must be connected passively or actively!
I
a
I
p
Current output active or passive
P
a
P
p
Pulse/frequency output active or passive
S
a
S
p
Status output/limit switch active or passive