Quickstart EN Instruction Manual

3 ELECTRICAL CONNECTIONS
16
IFC 300
www.krohne.com 08/2010 - 4000070303 - QS IFC 300 R06 en
3.3.3 Requirements for signal cables provided by the customer
Electrical safety
To EN 60811 (Low Voltage Directive) or equivalent national regulations.
Capacitance of the insulated conductors
Insulated conductor / insulated conductor < 50 pF/m
Insulated conductor / shield < 150 pF/m
Insulation resistance
R
iso
> 100 GΩ xkm
U
max
< 24 V
I
max
< 100 mA
Test voltages
Insulated conductor / inner shield 500 V
Insulated conductor / insulated conductor 1000 V
Insulated conductor / outer shield 1000 V
Twisting of the insulated conductors
At least 10 twists per meter, important for screening magnetic fields.
INFORMATION!
If the signal cable was not ordered, it is to be provided by the customer. The following
requirements regarding the electrical values of the signal cable must be observed: