3.10.2 Wall-mounted housing, electrical connection of the inputs and outputs
For frequencies above 100 Hz, shielded cables are to be used in order to reduce radiation
from electrical interferences (EMC). The shield must be electrically connected using
6.3 mm / 0.25" push-on connectors (insulation to DIN 46245) in the I/O terminal
compartment.
Terminal A+ is only operable in the basic version.
1 Open the housing cover
2 Push the prepared cables through the cable entry and connect them to the supplied connector
plugs 4.
3 Connect the shield if necessary.
4 Route the connector plugs with the clamped conductors into the sockets provided for that pur-
pose.
5 Close the housing cover.
DANGER!
All work on the electrical connections may only be carried out with the power disconnected. Take
note of the voltage data on the nameplate!
Figure 3-40: Connection of inputs and outputs in wall-mounted housing
INFORMATION!
Ensure that the housing gasket is properly fitted, clean and undamaged.