Operation
5.1 Start-up
Before connecting to power, please check that the system has been correctly installed.
This includes:
The device must be mechanically safe and mounted in compliance with the regulations.
Check the leak-tightness at the sleeve.
Make sure that the cable gland is tight or, as the case may be, the M12 plug is properly
screwed down.
The power connections must have been made in compliance with the regulations.
Check that the electrical operating data of the power supply are correct.
Switching on the power.
i Check for correct switching function.
5.2 Fault diagnosis and corrective action
Fault Cause Action / elimination
LED not "on" Sensor cap not in contact with
liquid product
-
Supply voltage < 12 V, permittivity
too low
Measure voltage at Pin 1 and 2
(M12: pin 1 and 3)
No switching output Cable break Check continuity of cables
Incorrect polarity of supply Reverse terminals 1 and 2 (M12:
terminal 1 and 3)
Short-circuit Check wiring