3.11 Measurement setup for level measurement
3.11.1 In open vessels with impulse line
The following points should be observed in this application:
Mount the differential pressure transmitter below the lower process connection so that the
impulse lines are always filled with liquid.
The low pressure side (L) is open to atmospheric pressure.
For measurements in products with solid content, the installation of separators and drain
valves is recommended to enable collection and removal of debris and sediment.
Figure 3-8: Application example
1 Tank
2 Impulse line
3 Differential pressure transmitter