3.11.2 In closed vessels with gas-filled impulse lines
The following points should be observed in this application:
Mount the differential pressure transmitter below the lower process connection so that the
impulse line is always filled with liquid.
The low pressure side (L) must always be connected above the maximum level.
For measurements of fluids with solid content, the installation of separators and drain valves
is recommended to enable collection and removal of debris and sediment.
Figure 3-9: Application example
1 Tank
2 Low-pressure line (L)
3 High-pressure line (H)
4 Differential pressure transmitter