3.11.3 In closed vessels with liquid / condensate filled impulse lines
The following points should be observed in this application:
• Mount the differential pressure transmitter below the lower process connection so that the
impulse lines are always filled with liquid.
• The low pressure side (L) must always be connected above the maximum level.
• For measurements of fluids with solid content, the installation of separators and drain valves
is recommended to enable collection and removal of debris and sediment.
Figure 3-10: Application example
1 Tank
2 Low-pressure line (L)
3 High-pressure line (H)
4 Differential pressure transmitter