4.2.3 Cable preparation
The device is connected with standard two-wire cable without shielding. If electromagnetic
interference is expected which is above the test values of EN 61326-1 for industrial areas, a
shielded cable should be used.
Check which outer diameter is suitable for the cable gland in order to ensure the sealing effect
according to the specified IP protection class.
5...9 mm / 0.20...0.35" (standard)
6...12 mm / 0.24...0.47" (optional)
10...14 mm / 0.40...0.55" (optional)
The terminals in the terminal compartment are designed for wire cross-sections of up to
1.5 mm². To ensure a proper connection, you should strip the cable 4050 mm / 1.6...2".
Figure 4-2: Stripping the cable
1 40...50 mm / 1.6...2"