5 START-UP
52
OPTIBAR DP 7060 C
www.krohne.com 04/2014 - 4003292001 - MA OPTIBAR DP 7060 C R01 en
5.6 Saving the device settings
We recommended noting the parameters and archiving them afterwards. They are thus available
for multiple use or service purposes. If the pressure transmitter is equipped with a display and
adjustment module, the most important data can be read out of the sensor into the display and
adjustment module. The data remain there permanently even if the sensor power supply fails. If
it is necessary to exchange the signal converter, the display and adjustment module is inserted
into the replacement device and the data are written into the signal converter under the menu
item "Copy device data".
5.6.1 Copy device settings
This function allows you to upload the selected data to the display and adjustment module or
download selected data to the signal converter. This function serves as a backup of the data,
since it is retained even if the power fails.
The following settings are saved:
all settings from the "Setup" and "Display" menus
the menu items "Reset" and "Date/Time"
Special parameters
Current output Current output mode Output characteristic 4...20 mA
Failure mode 3.6 mA
Current output variable Linear percent - Level
Current output, adjustment 0...100% = 4...20 mA
Current output min./max. Min. 3.8 mA
Max. 20.5 mA
Lock adjustment Unlock
Language English
Displayed value 1 Current output in %
Displayed value 2 Meas. cell temp. in °C
Backlight Off
Simulation Differential pressure
PIN 0000
Scaling Scaling variable Volume in L
Scaling format 0% = 0 L / 100% = 0 L
HART
®
mode
Address 0
Menu item Parameter Default