3 INSTALLATION
24
OPTIFLEX 2200 C/F
www.krohne.com 07/2013 - 4000668002 - HB OPTIFLEX 2200 R02 en
Weld a tube with an internal diameter of 12 mm / 0.5¨ to the bottom of the tank.
i Make sure the tube aligns with the process connection at the top of the tank.
Lower the probe into the tank.
Put the end of the probe into the tube.
The probe counterweight has a hole with an M8 internal thread. The other probe end options are
given in the illustration.
Single rod Ø8 mm / 0.3¨
Figure 3-14: How to attach a single rod probe to keep it straight
Single cable Ø4 mm / 0.15¨
Figure 3-15: How to attach a Ø4 mm / 0.15¨ single cable probe to keep it straight
1 Probe with threaded end
2 Probe with turnbuckle
3 Probe with chuck
4 If you chose a chuck to anchor the probe, we recommend that you fit a ferrule (metal sheath - not supplied) at the
bottom of the loop to prevent cable wear
CAUTION!
If your device has a chuck, you must recalculate the probe length. For the procedure, refer to
How to decrease the length of probes on page 89
. If the device is not set to the correct probe
length, it is possible that the device will not measure correctly.